Tobacco Institute
Two Indoor Air Quality Investigations - Oceans Apart
Fields
- Type
- SPEECH/PRESENTATION
- Ending Date
- 29 Jun 1990
- Named Person
- Hedge, A.
- Sterling, T.D.
- Sterling, E.M.
- Collett, C.W.
- Dickson, C.O.
- Sterling, D.A.
- Nie, V.
- Sterling, T.D.
- Named Organization
- Hewlett Packard
- Gilian Instrument
- Niosh
- Ashrae
- American Conference Governmental Indus
- Environmental
- Gilian Instrument
- Author (Organization)
- Air & Waste Management Association
- Author
- Turner, S. 1
- Litigation
- Dunn
- Date Loaded
- 02 Jun 1999
- UCSF Legacy ID
- gol91f00
Annotations
- 1. Turner, S. Author
- Affiliation:
Healthy Buildings International
- Affiliation:
Document Images
4
90-92.6
to slab by the tenants of this space, resulting in severely reduced return air
flow.
Originally the return air shaft travelled uninterrupted from the basement
to the penthouse, providing return air for both units. Apparently there were
air balance problems so a divider was built at the 13th floor level of the
shaft to completely separate the air from each unit.
System Condition. Both main air handling units were found to be operating on
100% return air with the outside air dampers completely closed on the days of
our inspection (maximum outside air temperature was 76°F). Both sets of
filters were in excellent condition and well fitted in their frames. The
filter chambers themselves were clean. There was some slime accumulation and
standing water associated with the condensate trays, and some light fungal
spots were found on flex ducting and insulation inside some of the chambers.
The VAV boxes examined in this inspection all appeared to be in generally
clean condition. Several of them had their dampers totally closed at the time
of our inspection.
The reheaters were equipped with low grade panel filters. Some of the
loose spray-on insulation had passed through these filters since some light
residues were caught up on the heater coils. In general, however, these units
were found to be clean.
Visual inspections of the air supply duct internals showed them to be
deposited with only trace or light amounts of brown granular materials.
Airborne sampling results for this building are shown on Table III. These
show low levels of carbon dioxide, carbon monoxide and nicotine, but
higherlevels of RSP, formaldehyde and in some areas airborne microbes.
In summary, this building reflected its relatively young age and
location. The building with a sealed "mirror" finish is typical of most
contemporary office structures. It was designed and built at the height of
the energy crisis and as a result, ventilation rates in the occupied spaces
are at a practical minimum both due to the relatively restrictive design of
the air supply system, and by its apparently routine operation with little or
no outside air. One might expect to see these low ventilation rates result in
high levels of carbon dioxide, but as seen in Table III, this is not the case.
This is because of relatively light occupant density, with less than half the
number of occupants than were found in Building A. Should the building ever
be occupied to occupant densities more common in government buildings, we
would expect these carbon dioxide levels to rise substantially, especially in
workday afternoons. A further contrast is found in the filtration system,
which was generally in an excellent, well maintained condition. This,
together with the fact that the building is relatively young, had lead to
systems which remain in a generally satisfactory clean condition. As a
result, dust levels were found to be generally satisfactory, with only a few
areas showing RSP levels over 75 µg/m3.
Several types of potentially allergenic fungi were isolated from the
mechanical rooms where visible growth was observed, but overall airborne
levels in the occupied areas were not excessive. We did note the presence of
formaldehyde, which while not at levels which breached the ASHRAE limit, did
11
TI DN 0004458
©

I
90-92.6
approach it in some areas. In general, other indoor pollutants in this
building, including tobacco smoke, were only found at low levels, but there
can be no doubt that this building was found to be poorly ventilated,
especially in the areas where complaints originated.
As an incidental point, this study complements other work16 in that
airborne measurements alone might fail to reveal the obvious causes of air
quality problems in a building such as this. While individual pollutant
levels remain under acceptable standards, a knowledgeable and thorough
inspection of the mechanical systems helps to reveal not only the origin of
current complaints, but potential for future ones.
Recommendations for improvements in this building included opening of the
outside air dampers to allow in the minimum outside air ventilation rate of 20
cfm per person, as recommended in ASHRAE Standard 62-89. Also, that the
loading dock be equipped with signs instructing drivers to switch their
engines off; cleaning and sanitizing of the condensate trays and other areas
inside the main AHUs showing visible fungal growth; opening of the ceiling
void in areas where slab-to-slab partitioning had been erected; and review of
the VAV damper setting policy to ensure adequate fresh air delivery into the
occupied spaces.
DISCUSSION
A simplistic overview of these contrasting buildings indicates that the
older government building on the east coast suffered from very poor filtration
and relatively high levels of dirt, while the newer commercial office building
suffered mainly from ventilation related problems. The contrasting
engineering characteristics, however, gave rise to very similar complaints
from the building occupants. In our view, this demonstrates that at least at
the initial stages of an investigation, little information can be gained from
occupant questionnaires which will be ultimately useful in solving indoor air
quality problems.
Major flaws in air quality related operation and maintenance practices
need to be corrected first before indulging in questionnaires, or indeed, any
other disruptive practices such as occupant shuffling, carpet removal, or
smoking bans. Further problems with occupant questionnaires are likely to be
resistance to such an exercise by building management or occupant employers,
and the real possibility that questions on health symptoms generate occupant
anxiety and eventually lead to a "snowballing" political issue, uncontained by
the original and possibly quite genuine complaints. Premature removal of
suspect carpets or smoking bans before checking the engineering evaluation
would usually only provide temporary relief and other pollutant accumulations
would probably manifest themselves at a later date.
Filtration. One of the biggest contrasts noted in these two buildings were
the filtration systems, one of which was rated as very poor, and the other as
excellent. Because choice and maintenance of filtration systems plays an
important part in indoor air quality, standards for rating them are crucial to
a successful engineering appraisal of an HVAC system. The current ASHRAE
Standard 52-76 requests that filter manufacturers specify both a weight test
and a dust spot test for each class of filter.
12
TI DN 0004459

90-92.6
i
The arrescance test involves a standardized synthetic dust consisting of
various particle sizes which is fed into the filter and the weight fraction of
the dust removed is determined. The synthetic dusts used are considerably
coarser than typical atmospheric dusts in general and indoor air particulate
in particular. Since most of the weight of dusts is in the larger particles,
the arrestance values are usually high, but these values give no indication of
the filter's capability to remove the smaller particles. In general,
arrestance values are virtually useless in choosing the suitability of filters
for indoor air. The alternative is the atmospheric dust spot test, where
atmospheric test dust is passed into the filter and the discoloration effect
of the cleaned air is compared with the incoming air. This test does include
many of the smaller particles since, although they are small and light, these
particles do still soil walls, etc. A disadvantage of this test exists due to
the variability of atmospheric dusts, which may cause the same filter to yield
different efficiencies at different times or locations. Even this atmospheric
dust spot test is unreliable at the smaller particle size range, i.e., below
1.0 microns in diameter. All the ASHRAE Atmospheric Dust Spot Test results
give efficiency ratings that are representative of particles greater than 1.0
micron. However, when the suitability of filters from a point of view of human
health is considered the sub-micron size particles are of most concern since
these are the ones that penetrate deep into the respiratory system and into
the lungs. In general, the sum of all the particles of less than 3.5 microns
in diameter is described as the Respirable Suspended Particulate (RSP),
although most of these particles are less than 1 micron in diameter.
In order to make assessments and encourage improvements of filtration
systems from the standpoint of an indoor air quality practitioner, some means
of comparing filters according to a nationally recognized test procedure that
addresses respirable particles is needed. One possible solution to this
requirement would be the development of a "standard indoor dust." HVAC
filters could then be assessed by their ability to remove this dust from an
airstream within their rated airflow capacity. Possibly, with the appropriate
standard testing equipment, this dust could be used to test an entire
filtration assembly in situ.
CONCLUSIONS
This study consisted of comprehensive evaluations of two identically
sized, yet contrasting office buildings. Despite similar complaints of
primarily upper respiratory problems in both buildings, air quality problems
were traced to entirely different origins. This calls into question the
usefulness of occupant questionnaires in such cases. The two buildings
demonstrate markedly different filtration characteristics in particular, which
highlights a need for a standard method of evaluation of in situ building
filtration systems. A standard indoor air test dust is proposed as a start in
developing such a method.
13
TI DN 0004460

9o-92.6
REFERENCES
1. A. Hedge, T.D. Sterling, E.M. Sterling, C.W. Collett, D.A.
Sterling and V. Nie, "Indoor Air Quality and Health in Two
Office Buildings with Different ventilation Systems,"
Environmental International 15 (1-6):115 (1989).
2. J.F. Brundage, R. McN. Scott, W.M. Lednar, D.W. Smith, R.N.
Miller, "Building-Associated Risk of Febrile Acute Respiratory
Disease in Army Trainees," JtA 259(14):2108 (1988).
3. H. Levin, "Sick Building Syndrome: Review and Exploration of
Causation Hypothesis and Control Methods," in The Human
Eauation: Health and Comfort, IAQ 89, ASHRAE, San Diego 1989,
pp. 263-274.
J.G. Robertson, "Indoor
Pollution: Sources, Effects and
Mitigation Strategies," in Proceedines of the 1989
International Symposium on Environmental Tobacco Smoke at
McGill Universitv, Lexington Books, Montreal, 1989, pp. 333-
355.
5. C. Molina, C.A.C. Pickering, 0. Valb,jorn, M. DeBortoli, Sick
Building_SYndrome. A Practical Guide, Report #4 Cost Project
613, Indoor Air Quality and Its Impact on Man, European
Concerted Action, Commission of the European Communitiies,
Luxembourg, 1989.
6. EPA, Determination of Nicotine in Indoor Air, Compendium of
Methods for the Determination of Air Pollutants in Indoor Air.
Method 1P-2A. U.S. Environmental Protection Agency, AREAL,
Research Triangle Park, 1989.
7. Bourdillon et al, "Airborne Bacteria Found in Factories and
Other Places," MRC Report #263, HMSO, London, pp. 257-263
(1948).
8. T. Wright, V.W. Green, H.J. Paulus, "Viable Microorganisms in
an Urban Atmosphere," JAPCA 19, p. 337 (1969).
9. P. Morey, et al, "Environmental Studies in Moldy Office
Buildings," Annals ACGIH, 10, pp. 21-35 (1984).
10. M.A. Dourin, "A Study of Atmospheric Mold Spores," Ann.
Allerev, 24, pp. 31-36 (1966).
11. G.T. Col, R.A. Sampson, "Mold Allergy," Ed. Y. AL-Doory and
J.F. Domson (1984).
12. EPA, National Primary and Secondary Ambient Air Oualitv
Standards, Code of Federal Regulations, Title 40 Part 50 (40
CFR 50), 1989.
14
TI DN 0004461

90-92.6
13. American Society of Heating, Refrigerating and Air
Conditioning Engineers, Ventilation for Accentable Indoor Air
va it , ASHRAE Standard 62-1989, Atlanta (1989).
14. American Conference of Governmental Industrial Hygienists
Threshold Limit Values and Biologjcal Exvosure Indices,
Cincinnati (1988-89).
15. American Society of Heating, Refrigerating and Air
Conditioning Engineers, Method of Testing Air-Cleanine Devices
used in General Ventilation for Removine Particulate Matter,
ASHRAE Standard 52-76, Atlanta (1976).
16. V.L. Putnam, J.E. Woods, T.A. Bosman, "Objective Measures and
Perceived Responses of Air Quality in Two Hospitals," ir.-The
Human Eauation: Health and Comfort, IAQ 89, ASHRAE, San Diego
1989, pp. 241-250.
NOTE TO EDITORS
Under the new federal copyright law,
publication rights to this paper are
retained by the author(s).
15
TI DN 0004462
