Tobacco Institute
Two Indoor Air Quality Investigations - Oceans Apart
Fields
- Type
- SPEECH/PRESENTATION
- Ending Date
- 29 Jun 1990
- Named Person
- Hedge, A.
- Sterling, T.D.
- Sterling, E.M.
- Collett, C.W.
- Dickson, C.O.
- Sterling, D.A.
- Nie, V.
- Named Organization
- Hewlett Packard
- Gilian Instrument
- Niosh
- Ashrae
- American Conference Governmental Indus
- Environmental
- Author (Organization)
- Air & Waste Management Association
- Author
- Turner, S. 1
- Litigation
- Dunn
- Date Loaded
- 02 Jun 1999
- UCSF Legacy ID
- gol91f00
Annotations
- 1. Turner, S. Author
- Affiliation:
Healthy Buildings International
- Affiliation:
Document Images
90-92.6
TWO INDOOR AIR QUALITY
INVESTIGATIONS -- OCEANS APART
Simon Turner
Healthy Buildings International Inc. (HBI)
Fairfax, Virginia
AiR & WASTE MANAGEMENT
A S S 0 C I A T t 0 N
Sirra 1907
For Presentation at the
83rd Annual Meeting & Exhibition
Pittsburgh, Pennsylvania
June 24-29, 1990
TI DN 0004448

90-92.6
INTRODUCTION
A commonly seen method of indoor air evaluations in buildings perceived
as "sick" involves an engineering study of a building in conjunction with a
questionnaire administered to its occupants. As a result we now have evidence
that tighter, air conditioned buildings generate higher incidence of upper
respiratory complaints than naturally ventilated buildings.1Z However, this
combination of engineering evaluation and occupant questionnaire as a
diagnostic method for sick buildings has not provided us with the ability to
predict the cause of indoor air problems from occupant symptoms.
One major reason for this appears to be that many common irritants found
in indoor air result in a similar range of upper respiratory symptoms. Many
diagnosed "sick" buildings are reported to have their causes rooted in
ventilation, filtration or hygiene problems which allow a mixture of low level
pollutants to build up.34 These irritate occupants in a complex and
possibly synergistic manner, the mechanism of which is largely unknown to us.
To demonstrate the range of engineering characteristics which can produce
similar complaints of sick building syndrome, this paper presents two case
histories of identically sized buildings, the studies of which were completed
in July of 1989. One of these buildings (designated as Building A) was
located in Washington D.C., and the other (designated as Building B) was
located in San Diego, California. Both buildings are 600,000 square feet in
size and a full description of their respective characteristics is found in
the results section.
Symptomology
The following symptoms were reported in Building A during the year
previous to this study: sneezing and/or coughing; sinus congestion; dry nasal
passages; post nasal drip; rashes and dry skin; headache; breathing
difficulties; sore throat; drowsiness; fatigue; eye irritation. In Building B
the following complaints were noted over the same period of time: odors;
headaches; shortness of breath; eye irritation; dizziness. These symptoms in
both buildings compare well with the classic symptomology of the sick building
syndrome as defined in the Commission of the European Communities Report --
Sick Building Syndrome, A Practical Guides which lists the symptoms as
follows: nasal irritation with nasal stuffiness; dryness and irritation of the
mucous membrane of the eye; dryness and irritation of the throat; skin dryness
and irritation; headaches, generalized lethargy and tiredness.
2
TI DN 0004449

METHODOLOGY
90-92.6
Although a standard approach was used to survey each building, it
required flexibility to cope with the different types of buildings examined.
Initial Walk Through
Since one of the objectives of this study was to assess maintenance
standards, each building evaluation commenced with an interview with the
personnel responsible for maintenance of the building. Questions were
designed to elicit operative details such as system on/off times; outside air,
return air and exhaust settings; scheduled maintenance routines; and complaint
areas. This part of the survey did not include questioning of the occupants
themselves, however. There was a walk through of each building to identify
obvious building configurations or design features which could influence air
quality in the occupied areas. This was followed by a visual inspection of
the internals of the building's ventilation system. This consisted of the
internal chambers of the air handling units including the condition of the
coils, fan chambers, humidifiers and condensate trays, and a detailed
assessment of the type, installation and condition of the filters in use.
A visual inspection was done of the internals of the main air supply
ductwork leaving each air handling unit. Where necessary, access was gained
to this ductwork by the installation of a small access port and the insertion
of a fiber optic borescope.
Qualitative Sampling
In each air handling unit and main air supply duct a series of samples
were also collected on cellulose ester filters for light microscopy analysis
and surface microbe samples were collected on Random Organism Detection and
Counting (RODAC) agar plates to be subsequently incubated, counted, and
identified.
A laser particle counter with a size selective inlet for sampling
particles with an aerodynamic diameter of 0.5 microns and above (Met One Inc.,
Oregon) was used to count particles inside the ductwork. At least two points
were sampled inside each major run of ductwork. This qualitative information
on the building, along with the location of the samples and the building
engineer questionnaire was prepared on a set of standard field notes to ensure
consistency.
Quantitative Air Sampling
Due to time constraints, a quantitative assessment of air volume flows
in, around and out of each building was outside the scope of this work.
Instead, other measurements, such as that for carbon dioxide, were used to
assess ventilation rates.
A set of locations were identified in each building to be used for
quantitative airborne sampling. These locations were spread evenly throughout
the study area of each building with a minimum of two locations per floor, as
3
TI DN 0004450

90-92.6
well as an outdoor control sample point. The following parameters were
measured at each location where relevant and appropriate:
o Respirable airborne particle counts using a piezoelectric microbalance
(TSI, Inc., St. Paul, Minnesota). This microbalance measures particles
in the 0.01 to 3.5 micrometer size range. It has a nominal sensitivity
of 180 micrograms per Hz and was used in the 120 second mode. Flow rate
through the piezobalance was periodically checked at one liter per minute
with a bubble flow meter, and the sensor was cleaned with alcohol swabs
after every five measurements. The unit is factory calibrated with
diluted welding fumes which have shown equivalence to indoor RSPs to
±10%. The lower detection limit was set at 10 Ngm"3.
o Carbon dioxide levels using a non-dispersive infrared absorption portable
gas analyzer, sensitive to 50 ppm (C02). Accuracy is ±29 over full scale
(CEA Instruments, Inc., Emerson, New Jersey). Periodic calibration of
the instrument was with a factory supplied span gas of 5.000 ppm COZ.
Zero was set with dry nitrogen gas and the lower detection limit was set
at 50 ppm.
o Carbon monoxide concentrations using a controlled potential electrolysis
detector, accurate to 10% full scale (Sensidyne Inc., Largo, Florida).
Periodic calibration of the instrument was with a factory supplied span
gas of 50 ppm carbon monoxide. The minimum detection limit was set at I
ppm.
o Airborne nicotine (after Ogden et al)6 with a personal universal flow
sampling pump (SKC Inc., Eighty-Four, Pennsylvania) drawing air at one
liter per minute for a period of one hour through unfiltered XAD4
absorbent resin tubes which collected a portion of particulate as well as
gaseous phase nicotine. Each tube contained an 80 mg front and 40 mg
rear portion of resin to detect any sample break-through. Samples
showing reduced collection efficiency, where nicotine was found in the
rear tube above our detection limit, were rejected. Samples were
desorbed into ethyl acetate containing 0.01% triethylamine and analyzed
with gas chromatography (fused silica DS-5 column and thermionic-specific
nitrogen-phosphorus detector, Hewlett Packard Model 5880A). Sampling
pumps were calibrated daily to one liter per minute with a"Gilibrator"
bubble flow meter (Gilian Instrument Corporation, Wayne, New Jersey).
The gas chromatograph was calibrated with freshly prepared nicotine
standards. All samples and blanks were doped with an internal standard.
Results are expressed in total micrograms converted to µgm-3, and the
detection limit for our sampling rate of lmin'1 for a one hour period was
1.6 µgm-3 of air. Supplemental measurements of carbon dioxide,
temperature, and relative humidities were also made at each location, so
that an assessment of environmental tobacco smoke levels as a whole could
be made.
o Temperature using a miniature platinum Pt 100 resistance sensor,
conforming to 1/2DIN 43760, Class A (The Dickson Company, Addison,
Illinois). Resolution was to 0.06C and accuracy was ±0.3°C. The unit
was factory calibrated and checked periodically against dry bulb
thermometers.
4
T1 DN 0004451

90.92.6
1
o Relative humidity using a chromed layered capacitative electrode (Dickson
Company, Addison, Illinois). Resolution was 0.18 relative humidity and
accuracy was to ±0.28 relative humidity at 23°C. Temperature drift was
±0.05% relative humidity per 1.1"C. The unit was pre-calibrated with a
factory supplied salt solution containing lithium chloride (12% relative
humidity) and sodium chloride (75% relative humidity).
The following parameters were measured in at least two selected locations in
each building:
o Miscellaneous gases using Gastec calibrated detector tubes (Sensidyne
Inc., Largo, Florida) as follows; nitrogen dioxide (DL - 0.2 ppm); low
range hydrocarbons (DL - 0.01%); high range hydrocarbons (DL - 20 ppm);
ozone (DL - 0.05 ppm); ammonia (DL - 0.15 ppm); sulphur dioxide (DL - 0.1
ppm). An outdoor control was taken at each building. These screening
measurements have an accuracy of approximately ±25%.
0 Airborne microbial counts using a centrifugal air sampler employing
impaction onto an agar lined drum (Biotest Diagnostics, Frankfurt, W.
Germany). The sampler had a separation volume of 40 lmin'1 and each agar
strip was exposed for a two minute period. A GK-A culture medium strip
was used which is suitable for total counts. Incubation was at 30 to
35°C for 48 hours, followed by counting and species identification. An
outdoor control was taken at each building.
o Formaldehyde using midget impingers containing sodium bisulphite followed
by spectrophotometric analysis, after NIOSH Method P6CAM 125N (now NIOSH
Method 3500). Accuracy is approximately ±10%, and detection limit was
set at 0.01 ppm.
Standards
The visual inspections provided evidence of the physical state of the air
handling plant and how it was being operated and maintained. The levels of
the airborne pollutants measured were compared with recognized standards where
they were available, where none existed they were compared with levels which
in HBI's experience have been found to be satisfactory. Table I shows the
parameters measured and standards used to assess air quality in the buildings.
Microbes
There are no established standards for airborne microbes in the indoor
air of office or other commercial buildings, although over many years attempts
have been made to set acceptable upper limits.7,8q Based on the experience
gained in more than 63 million square feet of building space HBI suggest an
upper acceptable limit of 750 colony forming units per cubic meter of air with
the provision that if the total airborne count is lower but species known to
cause allergies or infections are identified even this figure may be
unacceptable and steps should be taken to control them. From the results of
more than 200 studies world-widelo members of the same four fungal genera,
namely cladosporium, penicillium, aspergillus and alternaria, have been found
to account for the highest mean percentages isolated and from data based on
skin reactivity studies" the same four types constituted the most prevalent
5
%~W
TI DN 0004452

90-92.6
Table I. Parameters measured, standards and sources.
Parameter Standard ou ce
Carbon dioxide 800 ppm HBI*
Carbon monoxide 9 ppm EPA12
Respirable Suspended Particulates 75 ug/m3 HBI**
Microbes 750 cfu m3
~ HBI**
Nicotine 50 ug/m HBI (ASHRAE***)
Ozone 0.05 ppm ASHRAE
Formaldehyde 0.1 ppm HBI (ASHRAE***)
Temperature 20 to 26°C ASHRAE
Relative Humidity 20 to 70% ASHRAE
* HBI modification of American Society of Heating, Refrigerating and Air
Conditioning Engineers Standard, ASHRAE 62-1989"
** Suggested upper acceptable limit based on HBI experience.4
*** ASHRAE modification of American Conference of Governmental Industrial
Hygienists (ACGIH) recommendation14
fungi involved in allergic respiratory diseases with 85% of patients found to
be allergic to one or more members of these fungal genera. The bacterial
species which have been isolated from surface and air samples in the indoor
environment and which can cause infections in people include members of the
staphylococcus, pseudomonas and flavobacterium groups.
Ventilation
Good ventilation for commercial office buildings is defined by ASHRAE,
who in their recently published Standard 62-1989, 'Ventilation for Acceptable
Indoor Air Quality,"13 call for either a minimum intake of 20 cubic feet per
minute of outside air per person at all times of building occupancy, or,
evidence by measurements that no indoor air pollutants are accumulating in the
building air in unacceptable amounts.
An analysis of HBI Indoor Air Quality Investigations over the period from
1981 to 1988,4 given in Table II, shows that where the ventilation status of a
Table II. Pollutant ranges for well and poorly ventilated
buildings from HBI experience.4
Pollutant
i1IlLEs Ventilation Status
Good Poor
Carbon dioxide ppm 400-700 800-2,500
Carbon monoxide ppm 0-5 10-25
Respirable Suspended Particulates 20-60 70-200
Microbes cfu/m3 50-600 700-2,000
Nicotine ug/m3 0-10 50-100
Formaldehyde ppm 0-0.05 0.06-0.25
6
TI DN 0004453

90-92.6
building is good the levels of airborne pollutants are found in low and
acceptable levels; where ventilation is inadequate then they are found in
correspondingly higher and unacceptable levels.
RESULTS
Characteristics of Building A
S,,wstem Descristion. Building A is approximately 50 years o1d with six
occupied floors, five above ground and one underground basement level. The
building comprises an area of approximately 605,000 square feet and houses
about 3,500 government employees.
Heating, air conditioning and ventilation of the building is provided for
by approximately 103 air handlers. Many of these units are located throughout
the floor space of each level and generally serve adjacent or proximal areas
close to the air handler. The larger air handlers, those serving designated
areas on a number of floors, are located in the penthouse. A number of other
large air handlers, serving large spaces on the first floor, are located in
various fan rooms in the basement. Our study focused on a representative
number of both the penthouse and basement air handling units and the
associated systems.
The design of the air handling system was such that relatively large
volumes of outside air could be drawn in through either the penthouse or the
basement units, through banks of poor quality one inch spun glass filters.
The penthouse units were typical of air handling systems of this age in that
they were constructed with dual chambers, one each for heating and cooling.
Vertical air supply shafts then deliver air either to ceiling-mounted supply
diffusers in the interior areas of the building, or forced air induction units
(FAIU) around the perimeter. The return system for this building consists of
3'x3' return grilles set in corridors which lead back to large vertical return
shafts connecting with either the basement or penthouse units.
Exhaust is provided by large exhaust fans located in the penthouse which
draw ducted air from grilles in the ceilings on each floor. This is
supplemented with toilet exhaust. The air volumes in this building were once
controlled by static pressure sensors in the floor spaces which worked in
conjunction with vortex vanes on the air handling unit air supply fans, along
with an air relief mechanism. This volume control system had been
disconnected, allowing the building to run essentially as a constant volume
system. The system was set to run 24 hours a day.
The original air handling system described above has been added to as the
building underwent renovations over the course of time.
System Condition. Both the penthouse and the basement units were in need of
some maintenance work to bring them up to a satisfactory condition. The
preheat coils in the penthouse unit were not fitted with filters and were
found to be clogged with dirt. Other filters were found to be loosely fitted
and therefore operating at severely reduced efficiency. Virtually all of the
units were found to be in need of a vacuuming out of loose dirt. The
condensate trays and humidifier reservoirs were often in poor condition and
7
TI DN 000445,

(
90-92.6
contained stagnant water. Some badly damaged internal insulation was also
noted which was releasing loa:e fibrous glass into the airstream. A number of
the FAIUs were inspected and found to be very dirty.
Visual inspection of the supply duct internals showed them to be
moderately deposited with mixed granular dirt. They would prove difficult or
impossible to clean due to poor access and the use of asbestos insulants in
many areas.
Airborne sampling results are shown in Table III. These show low levels
of gases measured, such as carbon dioxide, carbon monoxide, formaldehyde and
also nicotine and respirable sized particles. Higher levels of airborne
microbes were found in some areas.
Table III. Selected quantitative sampling results.
Type test Buildine A Buildine B
Respirable sized Outdoors 40 10
particles (pg/m3) Mean - Indoors 31 19
Range 20-50 10-85
Standard deviation 9.2 16.0
Carbon dioxide (ppm) Outdoors 350 350
Mean - Indoors 509 608
Range 350-750 450-800
Standard deviation 91 75
Carbon monoxide (ppm) Outdoors 3 2
Mean - Indoors 2.6 1.9
Range 2-3 1-2
Standard deviation 0.48 0.35
Formaldehyde (ppm) Outdoors (assumed) <0.01 <0.01
Mean - Indoors 0.016 0.048
Range <0.01-0.02 0.01-0.10
Standard deviation 0.008 0.03
Temperature ('F) Outdoors 89.5 76.0
Mean - Indoors 76.8 73.0
Range 73-79 72-74
Standard deviation 1.3 0.69
Relative humidity (!) Outdoors 87 44
Mean - Indoors 62.7 37.1
Range 50-69 32-48
Standard deviation 3.9 3.9
Nicotine (pg/m3) Outdoors (assumed) <1.6 <1.6
(discretionary Mean - Indoors <1.6 2.9
smoking areas) Range <1.6 2.1-3.7
Standard deviation 0 0.8
8
i.i
TI DN 0004455

90-92.6
Table III. Seleited quantitative sampling resul-s (continued).
Tvoe test
Airborne microbes
(cfu/m3)
Building A Buildine B
Outdoors >1250 700
Mean - Indoors 707 457
Range 138->1250 185-816
Standard deviation 499 153
Fungal species Penicillium Aspergillus
identified from Aspergillus Cladosporium
surface and airborne Penicillium
sampling Scopulariopsis
Acremonium
Candida
Oospora
Chrysosporium
Miscellaneous gases (nitrogen dioxide, lower and higher range hydrocarbons,
ozone, ammonia, and sulphur dioxide); none of these were found above the
detection limit of the method used and are, therefore, not included in this
table.
Rev:
ppm - parts per million
µg/m3 - micrograms per cubic meter
cfu/m3 - colony forming units per cubic meter
In summary, this building reflected the age in which it was designed in
that it was built long before the energy crisis which forced ventilation
system designers to create more energy efficient systems. As a result, it is
equipped with a large number of air handling units bringing in relatively high
volumes of outside air, and expelling equally large volumes of air via a
powerful exhaust system. This is reflected in the carbon dioxide measurements
which indicate the building, overall, was well ventilated. The powerful
exhaust system also appeared to be removing internally generated particulates
which were not at excessive levels. The building, however, was fitted with a
very poor filtration system, and as a result of this along with its age, the
air handling systems were dirty. These high dirt loads subsequently gave rise
to relatively high airborne microbe counts and the presence of some species of
fungi which are known to cause allergenic reactions in sensitive individuals,
Most other commonly found indoor pollutants, including carbon monoxide,
environmental tobacco smoke, and oxides of nitrogen were found at low levels
in most areas, primarily because of the satisfactory ventilation rates.
Recommendations for improvements in this building included a substantial
upgrade of the filtration system to at least filtering rated to 35% by
ASHRAE's atmospheric dust spot test (ASHRAE 52-76);15 cleaning work in each
air handling unit, and FAIU repair and biocidal treatment of the condensate
trays; decommissioning of the humidifier reservoirs during the humid east
coast summer months; repair to loose internal insulation; and the treatment of
cleaned surfaces with a broad spectrum biocidal spray.
9
TI DN o004456

90-92.6
Building B
Svstem Descrintion. Building B is approximately eight years old and stands
24 stories tall. There is a basement level, a mezzanine above the first
floor, and a penthouse that houses one of two mechanical equipment rooms, the
other being in the basement.
The building comprises approximately 600,000 square feet of space and
housed close to 1,200 commercial office tenants at the time of our inspection.
Conditioned air is provided by two main air handler units (AHUs), one located
in the basement and the other in the penthouse. Each are served by a cooling
tower mounted on the roof and chillers located in the basement.
The system is a variable air volume (VAV) type delivering air via 14 VAV
boxes located in the ceiling voids of each floor. Heating requirements are
met by perimeter located reheat boxes in the ceiling voids, there being no
requirement to heat the core of the building. The two main air handlers
operate in a similar manner.
Fresh air is drawn to the building and fed to the air handlers via
openings in the second floor and on the rooftop. One obvious potential
problem with the second floor AHU concerned the location of its fresh air
intake. The intake was located directly over the loading bay and was also
immediately adjacent to the garage. During high activity in the garage and
high use of the loading dock, it is probable that vehicle exhaust fumes
(especially hot diesel fumes from trucks using the loading area) will be
induced into the air intake. This could result in complaints on any of the
floors, 1 through 13, served by this unit.
In each air handling unit, the air then passes into a mixing chamber and
then through a set of high quality two inch pleated panel filters. The single
chamber heating and cooling system is followed by a twin variable pitch air
supply fan arrangement, which feeds supply air into round vertical air supply
ducts to the various floors.
On each floor the final supply to the occupied areas was via 14 variable
air volume boxes per floor. The VAV boxes were designed with a minimum set
point for the dampers. However, this setting resulted in too powerful an air
jet at the diffusers so the units were modified to do away with the minimum
setting and subsequently they can close completely. The perimeter areas on
each floor were equipped with reheat boxes which draw in return air from the
ceiling void through a spun glass furnace filter, then an electric heating
coil, and then back into the occupied areas.
Return air from the office space enters the ceiling void through light
troffers. The ceiling void acts as a return air plenum and thus it is
important that these plenums are not compartmentalized. Air moves across the
void to stub ducts linking each void to the return air shaft located on the
east side of the building. The low rise AHU draws air down this return shaft
into the basement. The return air can be either exhausted through a set of
eight exhaust fans per AHU, or it is mixed with a portion of fresh air in a
prefilter chamber to start the cycle over again. It was noted at this
inspection that the tenth floor ceiling voids had been partitioned from slab
10
.J
TI DN 0004457
