Philip Morris
Fields
- Type
- SCRT, REPORT, SCIENTIFIC
- BIBL, BIBLIOGRAPHY
- CHAR, CHART, GRAPH, TABLE, MAPS
- BIBL, BIBLIOGRAPHY
- Area
- CENTRAL FILES/PRE-DB WAREHOUSE
- Characteristic
- EXTR, EXTRA
- MISS, MISSING PAGES
- Named Organization
- Ashrae, American Society of Heating, Refrigerating + Air-Conditioning Engineers
- Building Energy Utilization Lab
- Engineering Research Inst
- Ia State Univ
- Building Energy Utilization Lab
- Named Person
- Szokolay
- Document File
- 2021578674/2021578937/Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control
- Litigation
- Ppla/Produced
- Master ID
- 2021578685/8936
Related Documents:- 2021578685-8936 Period 2 Project Report Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control 920516 to 930831
- 2021578705-8708 Comparative Evaluation of Displacement Ventilation and Conventional Vav Systems for Indoor Air Quality Control
- 2021578709
- 2021578711-8717 Proposal to Philip Morris, Usa for Continuation of Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control
- 2021578719-8753 Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control Status Report: Design Process of the Research and Demonstration Facility Phase II
- 2021578755-8762 Indoor Environment Program Meeting with the Science Advisory Committee 930129 Minutes and Action Items
- 2021578764-8780 Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control Progress Report 920515 - 921115
- 2021578781-8785 Appendix A Abstracts for Indoor Air '93
- 2021578786-8790 Appendix B Project Overview Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control
- 2021578791-8798 Appendix C Performance Criteria
- 2021578800-8815 Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control Progress Report 921116 - 930215
- 2021578816-8824 Appendix A Minutes of the 930129 Science Advisory Committee Meeting
- 2021578825-8831 Appendix B Rational Building Performance and Prescriptive Criteria for Improved Indoor Environmental Quality
- 2021578832-8838 Appendix C Modeling the Thermal and Indoor Air Quality Performance of Vertical Displacement Ventilation Systems
- 2021578839-8845 Appendix D Evaluation of A Vertical Displacement Ventilation System
- 2021578847-8855 Design and Construction of A Facility for Research and Demonstration of Healthy Building Concepts
- 2021578856 Indoor Air '93 Proceedings of the 6th International Conference on Indoor Air Quality and Climate Volume 3. Combustion Products, Risk Assessment, Policies
- 2021578857-8862 Rational Building Performance and Prescriptive Criteria for Improved Indoor Environmental Quality
- 2021578863 Modeling the Thermal and Indoor Air Quality Performance of Vertical Displacement Ventilation Systems
- 2021578864 Indoor Air '93 Proceedings of the 6th International Conference on Indoor Air Quality and Climate Volume 5. Ventilation
- 2021578865-8870 Modeling the Thermal and Indoor Air Quality Performance of Vertical Displacement Ventilation Systems
- 2021578871 Evaluation of A Vertical Displacement Ventilation System
- 2021578872 Indoor Air '93 Proceedings of the 6th International Conference on Indoor Air Quality and Climate Volume 5. Ventilation
- 2021578873-8878 Evaluation of A Vertical Displacement Ventilation System
- 2021578879 A Characterization of Methodologies for Assessing Human Responses to the Indoor Environment
- 2021578880 Indoor Air '93 Proceedings of the 6th International Conference on Indoor Air Quality and Climate Volume 1. Health Effects
- 2021578881-8886 A Characterization of Methodologies for Assessing Human Responses to the Indoor Environment
- 2021578887-8897 A Case Study: Cost Implications for Hvac Commissioning
- 2021578898-8903 Appendix A Specification Section 15995: Commissioning of Hvac System Contract Specifications for Architecture Research and Demonstration Facility Phase II, Virginia Polytechnic Institute and State University, College of Architecture and Urban Studies, Blacksburg Virginia, Rev. 11 930800
- 2021578905 Fluid Filtration: Gas Volume I A Symposium Sponsored by Astm Committee F-21 on Filtration and the American Program Committee of the Filtration Society Philadelphia, Pa, 861020 - 861022
- 2021578906-8926 Filtration As A Method for Air Quality Control in Occupied Spaces
- 2021578927 Indoor Air Volume 5 Buildings, Ventilation and Thermal Climate
- 2021578934-8936 Economic Modeling of Vav and Vdv Systems in Rdf II
- Site
- R107
- Date Loaded
- 07 Jan 1999
- UCSF Legacy ID
- hlc33e00
Document Images
4R(,.
Evaluation Method
i
Environmental Acceptability
,5zokolay defines the environment as "t he stimulus field to which
man responds in some way "(3). For our purposes, the environment will
be restricted to the stimuli (or stressors) influenced by the building.
They can be classified in 5 categories: spatial, visual, thermal.,
acoustical environments and indoor air quality. Criteria for
environmental quality are desIgned to protect the occupant. from
excessive responses (strain), physiological, pathological or
psychological, resulting from exposure to these stimuli. The criterionn
of acceptability will be used to assess the building environmental
performance. Acceptability is defined as the percentage of people who
will not express dissatisfaction with the environmental conditions.
Acceptability is based on physiological data and subjective individual
responses (4,5,6,7).
Envrgy Requirement
In an ideal building, the natural environmental conditions, i.e.,
the conditions that exist when all environmental control systems are
turned off, would meet the requirements for acceptability during all
occupied periods. The difference between the natural conditions and the
acceptable conditions is a measure of the passive performance - or lack
thereof - of the building. Energy requirement is used to assess the
passive performance; it is defined as the amount of energy strictly
necessary to upgrade the environment from natural to acceptable
conditions during occupied hours. Energy requirement depends on:
- the function of the building (occupancy schedules, tvpe of
activity),
- the passive behavior of the building (natural ventilation,
insulation, passive solar strategies, natural lighting),
- the climatic conditions.
Energy Efficiency
Energy efficiency is defined as the ratio of energy requirement to
energy consumption over a given period of time. Energy efficiency is a
function of:
- the individual efficiencies of the components of the energy
transformation and distribution systems,
- the performance of the control strategies.
Experimental Procedure, Results and Discussion
The objective of the experiment described here, is to compare the
performances of an old and a new building by applying the evaluation
model described in the previous part. The two buildings a~e situated on
the Iowa State University campus. The :,ld one is a 6500 m2 brick
building constructed in 1900 and the new one is a 15,500 m facility
which was completed in 1976. Both buildings include only classrooms and
offices.

487
Energy Requirements
Energy requirements were computed for a typical classroom in each
building using weather data of average January, March, May and July
days. North and South exposure were examined in each 2 ase. All
requirements are computed on a daily basis and on a m floor area basis.
Energy flows are evaluated at the boundary of the occupied space (1 MJ
of lighting has the same weight as 1 MJ of heating or cooling in the
energy balance). The energy requirements are shown with their signs
(positive when energy is supplied to the space) in Table 1. The energy
requirements-are computed independently for lighting, ventilation, and
thermal control. The total energy requirement is the sum of the
absolute values of the requirements for lighting, ventilation and
thermal control.
Lighting The lights are on during all occupied periods, as was the
case during the monitoring of the two buildings.
Ventilation Ventilation energy requirement is computed as the
amount of energy necessary to bring the amount of outdoor air required
for ventilation to room conditions. The effect of infiltration on
indoor air quality is neglected. The ventilation system is operated
during the 9 hours of occupancy and is designed to handle the maximum
occupancy load. The outdoor air requirements are 2.5 t/(s' person) (4).
Ventilation energy requirements were computed using hour by hour steady
state equations.
Thermal Environment. Thermal acceptability requires operative
temperatures around 21.7°C in the winter and 24.4°C in the summer (5).
The thermal control energy requirement is computed from hour by hour
energy balances. The ASHRAE methods of Total Equivalent Temperature
Difference (TETD) an& Solar Heat Gain Factor (SHGF) are used to compute
the hourly energy flows through the wall's and the window respectively
(7):. Temperature set backs were assumed for unoccupied periods.
As can be seen from Table 1, energy requirements in the neww
building are smaller than those of the old one in all cases examined (5
to 47% reduction). The assumptions used for the calculations of energy
requirements reflect the most current strategies for environmental
control. However, there are strategies which can result in
significantly reduced energy requirements: the amount of artificial
lighting can be controlled by illuminance sensors and the amount of
fresh air brought to the space regulated according to the C02
concentration.
Energy Efficiency
Energy efficiency is the ratio of energy requirement and energy
consumption, the latter being the sum of all energy flows supplied to
environmental control systems. Energy requirements and consumptions of
the two buildings are shown on Figure 1, and the efficiencies, on Figure
2.
For the old building the efficiencies of over 100% in the summer
result from the fact that the acceptability requirements are not met (no
coaling paovided). Because the monitoring of the building only covered

4RR
a two week period in April, it was not possibIe to evaluate the penalty
of not providing cooling in terms of thermal acceptability. It can be
seen from Figure 2 that the efficiency of the old building in peak
heating mode is significantly smaller than that of the new one. It
could be expected that, if the old building was to provide cooling, its
efficiency in peak cooling mode would be smaller also.
In the new building, much of the energy necessary for thermal
control is needed for cooling, even in January. The use of cold outside
air until May makes it very easy to meet thp requirement with a very
smalli energy consumption. This explains the high efficiency in the
winter time. In the summertime, the cooling has to he achieved by
refrigeration and this results in much lower efficiency.
Improvements achieved in the energy efficiency of the new, building,
although significant, are not as large as one could er.pect, considering
the improvements in building technology which took place between 1900
and 1976. Two factors explain this:
- The environmental systems are designed to meet the maximum
load, However, most of the time in a new building, the load is much
smaller than the design load and the systems run at a small fraction of
their capacity and are therefore less efficient.
- Because in a new building, the same space may require heating
and cooling during the same day, because the loads are often smal.ler
than capacity, and because of low first cost constraints, the control
strategies are inefficient.
The energy consumed by a building usually comprises different types
of energy, all of which have different costs. The energy efficiency as
define&here does not take these differences into account. Other
efficiencies of interest could differentiate between:
- primary and non primary energy
- renewable and non renewable energy
- purchased and non purchased energy
Conclusion
Energy requirement measures the passive energy performance off a
building. It integrates the acceptability requirements. It relates
specifically to the architectural features. Energy requirement can be
used as a tool to help design environmental systems and control
strategies whi.ch are best adapted to the specific charactoristics of a
given building. It can also be used to specify design goals for future
constructions.
Energy efficiency measures the active performance of the
environmental systems. It can be used as a single iindex to compare
different buildings, at different locations and can be used as a
standard both for existing and future buil.dings.
Acknowledgement
The study described here was conducted at lowa Stite t1niversity and
was made possihle through the support of the Rnilding BnerRy iltilization
Laboratory and the Engineering Research Institute.

489
References
1. Shell Oil Company. "The National Energy Outlook 1980-2000."
Houston, Texas: Shell Oil Company, 1980.
2. Contothanassis, Yannis P. Rehabilitation as an Alternative to New
Construction in Iowa. Master of Architecture thesis. Iowa State
University, Ames, Iowa 1981.
3. Szokolay,, A.V. Environmental Science Handbook. New York: John
Wiley and Sons, 1980.
4. ASHRAE. "Ventilation for Acceptable Indoor Air Quality." ASHRAE
Standard 62-1981. American Society of Heating, Refrigerating and Air
Conditioning Engineers, Inc., Atlanta, GA, 1981.
5. ANSI/ASHRAE. "Thermal Environmental Conditions for Human
Occupancy." ASHRAE Standard 55-1981. American Society of Heating,
Refrigerating and Air Conditioning Engineers, Inc., Atlanta, GA, 1981.
6: Kaufman, J.E., ed. IES Lighting Handbook. Sixth edition. Volume
1, reference volume. New York: Illuminating Engineering Society, 1981.
7. ASHRAE. Handbook of Fundamentals. Atlanta, Georgia: American
Society of Heating, Refrigerating and Air Conditioning Engineers, Inc.,
1981.
1120
x
I
I
tntrery r.quarea.nt. :
I Ilqntanq
= v.ntl.l.tloe
= TMr~.l eonerol
n
old ..«
buildinq
7
n.r" ren.vPtlon ..
Il'
Latent .nerqy
tnerqy.appll'.dte the .p.a.
tn.ryy.rer.et.d tron the .p.e.
Fig. 1. Energy requirements and
energy consumption for
an old and a new space.
(Nbr~h exposure;
PIJ/m .dav).
c
too
v
i
>.
: ao
e
S
0
i .J
.
40
20
II,
I Old bastdinq
+
+\ (119.v Eulldlnq.
I
I
S
7
1
11 1
Snnt11
t- en.rry .ellei.ncy i. .bo.e 100% b.e.u.e eontrol.trateqae
r..alt sn .nerqy.r.qair...nty that ere t.ll.r than the
pr.dtRed on... (... .u.unptlows tor Pr.dtetaono en P. It
:I-[nerqr .[lica.ncy k. .eow 1CIOR b.e.r.e .eeePteHlllty
r.vuir~.nt er. nue ..t (m oeollnq pe.vtded)..
Fig. 2. Energy efficiency of
an old and a new spacg,
(North exposure; MJ/m day)

490
TABLE 1. Energ~ requirements of an old and a new occupied spaces
(MJ/m .day)
January March May July
Lighting
Ventilation sensible
latent
Thermal Control Sensible 0.50
1.16
0.43r 0.50
0.84
0.22 0.50
0.16
0. 0.50
-0.08
-0.21
O1d North
South
New North
I
South 3.84
-
2.38
-0.09
0.48
-0.28
0.44
77
-0 2.18
-
1.32
-0.39
0.33
-0.53
0.29
98
-0 0.59
-0.55
0.54
-1.33
0.16
-0.90
0.17
41
-1 -
-1.17
-2.02
-
-1.09
-
-1
59
Thermal Control Latent . . . .
Old
New -0.12
-0.36 -0.26
-0.39 -0.42
-0.39 -0.67
-0.47
Totals North old 6.05 4.00 2.22 2.63
New 3.21 2.81 2.11 2.35
South Old 4.68 3.53 2.95 3.48
New 3.66 3.22 2.63 2.85
