Philip Morris
Filtration As A Method for Air Quality Control in Occupied Spaces
Fields
- Author
- Krafthefer, B.C.
- Woods, J.E.
- Type
- PSCI, PUBLICATION SCIENTIFIC
- ABST, ABSTRACT
- BIBL, BIBLIOGRAPHY
- CHAR, CHART, GRAPH, TABLE, MAPS
- DRAW, DRAWING
- ABST, ABSTRACT
- Document File
- 2021578674/2021578937/Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control
- Site
- R107
- Author (Organization)
- Honeywell Energy Products Center
- Honeywell Physical Sciences Center
- Master ID
- 2021578685/8936
Related Documents:- 2021578685-8936 Period 2 Project Report Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control 920516 to 930831
- 2021578705-8708 Comparative Evaluation of Displacement Ventilation and Conventional Vav Systems for Indoor Air Quality Control
- 2021578709
- 2021578711-8717 Proposal to Philip Morris, Usa for Continuation of Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control
- 2021578719-8753 Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control Status Report: Design Process of the Research and Demonstration Facility Phase II
- 2021578755-8762 Indoor Environment Program Meeting with the Science Advisory Committee 930129 Minutes and Action Items
- 2021578764-8780 Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control Progress Report 920515 - 921115
- 2021578781-8785 Appendix A Abstracts for Indoor Air '93
- 2021578786-8790 Appendix B Project Overview Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control
- 2021578791-8798 Appendix C Performance Criteria
- 2021578800-8815 Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control Progress Report 921116 - 930215
- 2021578816-8824 Appendix A Minutes of the 930129 Science Advisory Committee Meeting
- 2021578825-8831 Appendix B Rational Building Performance and Prescriptive Criteria for Improved Indoor Environmental Quality
- 2021578832-8838 Appendix C Modeling the Thermal and Indoor Air Quality Performance of Vertical Displacement Ventilation Systems
- 2021578839-8845 Appendix D Evaluation of A Vertical Displacement Ventilation System
- 2021578847-8855 Design and Construction of A Facility for Research and Demonstration of Healthy Building Concepts
- 2021578856 Indoor Air '93 Proceedings of the 6th International Conference on Indoor Air Quality and Climate Volume 3. Combustion Products, Risk Assessment, Policies
- 2021578857-8862 Rational Building Performance and Prescriptive Criteria for Improved Indoor Environmental Quality
- 2021578863 Modeling the Thermal and Indoor Air Quality Performance of Vertical Displacement Ventilation Systems
- 2021578864 Indoor Air '93 Proceedings of the 6th International Conference on Indoor Air Quality and Climate Volume 5. Ventilation
- 2021578865-8870 Modeling the Thermal and Indoor Air Quality Performance of Vertical Displacement Ventilation Systems
- 2021578871 Evaluation of A Vertical Displacement Ventilation System
- 2021578872 Indoor Air '93 Proceedings of the 6th International Conference on Indoor Air Quality and Climate Volume 5. Ventilation
- 2021578873-8878 Evaluation of A Vertical Displacement Ventilation System
- 2021578879 A Characterization of Methodologies for Assessing Human Responses to the Indoor Environment
- 2021578880 Indoor Air '93 Proceedings of the 6th International Conference on Indoor Air Quality and Climate Volume 1. Health Effects
- 2021578881-8886 A Characterization of Methodologies for Assessing Human Responses to the Indoor Environment
- 2021578887-8897 A Case Study: Cost Implications for Hvac Commissioning
- 2021578898-8903 Appendix A Specification Section 15995: Commissioning of Hvac System Contract Specifications for Architecture Research and Demonstration Facility Phase II, Virginia Polytechnic Institute and State University, College of Architecture and Urban Studies, Blacksburg Virginia, Rev. 11 930800
- 2021578905 Fluid Filtration: Gas Volume I A Symposium Sponsored by Astm Committee F-21 on Filtration and the American Program Committee of the Filtration Society Philadelphia, Pa, 861020 - 861022
- 2021578927 Indoor Air Volume 5 Buildings, Ventilation and Thermal Climate
- 2021578928-8932
- 2021578934-8936 Economic Modeling of Vav and Vdv Systems in Rdf II
- Litigation
- Ppla/Produced
- Characteristic
- EXTR, EXTRA
- Area
- CENTRAL FILES/PRE-DB WAREHOUSE
- Date Loaded
- 07 Jan 1999
- UCSF Legacy ID
- flc33e00
Document Images
James E. Woods and Brian C. Krafthefer
FILTRATICN AS A METHOD FOR AIR QUALITY CONTROL IN OCCUPIED SPACES
REFERENCE: Woods, J.E. and Krafthefer, B.C. "Filtration as a
Method for Air Quality Control in Occupied Spaces," Fluid
Filtration: Gas, Volume I, ASTM STP 975, R. R. Raber, Ed.,
American Society for Testing and Materials, Philadelphia,
1986.
ABSTRACT: Filtration, or removal control, is one of three
methods currently available to provide acceptable indoor air
quality in occupied spaces. While the other two methods,
source and dilution control, are primarily employed for
occupant needs, filtration has conventionally been used for
protection of components within the heating, ventilating, and
air conditioning systems. In this paper, filtration tech-
nology is reviewed with respect to current ventilation stand-
ards for occupants. The difference between ventilation and
air quality control is discussed in terms of acceptability
criteria and control methods. Parameters that relate these
terms are identified and control strategies are proposed that
can be used to optimize removal and dilution methods for
occupant acceptability and cost-effectiveness.
KEYWORDS: Ventilation, Indoor Air Quality, Control
Strategies, Removal Control, Filtration
Although filtration technology has been applied in heating, venti-
lating, and air conditioning (F1UAC) systems for more than fifty years,
its primary function has not been provision of health or comfort for
the occupants. Rather, filters are usually installed to protect the
components (e. e. , coils, fans, ductwork) within the HVAC systems f rom
dust and particulate loading. Only in special cases, such as critical
care areas in hospitals, have filters been installed in the systems
primarily for the protection of the occupants.. Otherwise, ventilation
with outdoor air has been depended upon to dilute particulate and
gaseous contaniiiants in occupied spaces to concentrations below those
Dr. Woods is Senior Engineering Manager, Honeywell Energy Products
Center, Golden Valley, MN 55422. Mr. Krafthefer is Principal
Research Scientist, Honeywell Physical Sciences Center, Bloomington,.
MN 55420.
193

194 FLUID FILTRATION: GAS
considered to te deleterious or annoying. However, with the advent of
energy conservation practices of the last decade, ventilation rates
have been generally reduced. As a result, many ventilation systems no
longer provide acceptable control of particulate and'gaseous contam-
inants. The objective of this paper is to describe control strategies
that can be used to optimize filtration and dilution for occupant
acceptability ar(d cost-effectiveness.
VENTILATION CONTROL
A'schematic of conventional HVAC systems, Figure 1, identifies the
catmon placements of filters (1]. In residential systems, filters are
usually placed in the return air duct as these systems normally use
1001; recirculated air. If outdoor air is supplied mechanically to the
system, a"pre-filter" may be installed, but usually dilution depends
on infiltration (i.e., uncontrolled air leakage through the building
envelope). Mechanical systems for commercial or institutional fa-
cilities may have filters installed either in the return air duct or
the "mixed-air" plenum. Note that the placement of these filters is
upstreamlof the major mechanical components in the system. This prac-
ti'ce is encouraged to achieve protection of the system from contamin-
ation. The effectiveness of this practice has recently been docu-
mented, and results indicate that significant energy and cost savings
can accrue over the lifetime of the system (2].
AIR.
EXHAUST CONDITIONING INFILTR
UNIT
ATION'. OTHER
AIR CLEANER
AIR CLEANER ATION'
LOC
LOCATION r'~~~~ _
~ 1
OUTDOOR-
AIR I i
(MAKEUP ~.
AIRI
ALTERNATE
_- I--t r _.~ F~
PAf11SFOR t ~ OTHER
HCCI/IL'UTATED - - AI/tYILANER
AIR -LOCATIONS
LOCAL
SUPPLY AIR ~ r/.-MAKEUP
CONDITIONED
SPACE
L_4
LOCAL
EXI/AUST
1 OCAI
VCNf11.AIlON
GENERAL \...- RETURN AIR
EXHAUST
l
EXFILrRAT1ON
Figure 1. Heating, ventilating, and air conditioning,system
schematic indicating variables for indoor air quality control.
(From Ref. 1)
Only In special cases have filters also been installed downstream
of the major components to provide clean air to the occupied space.
For example, in critical areas of hospitals, two filters are speci-
fied. The upstream filter (pre-filter) and the downstream (final)
filter must have minimum ASHRAE dust-spot efficiencies of 25S arid 85%,
respectively [3, y]

WOODS AND KRAFTHEFER ON OCCUPIED SPACES FILTAATION 195
While common practice indicates that filtration is used for con-
tamination control in only special cases, recognition of its general
application for ventilation control has existed for more than a de-
cade. In 197', the ASHRAE ventilation standard defined ventilation
air as: "that portion of supply air which comes from outside (out-
doors) plus any recirculated air that has been treated to maintain the
desired quality of air within a designated space" [5]. In that stand-
ard, minimum and recommended ventilation rates of acceptably clean
outdoor air were specified for numerous occupied spaces. That stand-
ard also allowed recirculation if adequate temperature and filtration
control were employed'. For the latter case, the outdoor air require-
ments could~be reduced to 33% of the tabulated values if particulate
filters were employed, and to 15% of the values if adsorption or other
gas removal equipment were employed. However, two constraints were
imposed:
1. the outdoor air quantity could not be less than 2.5 1/s (i.e.,
5 cubic feet per minute) per person; and
2. the maximum allowable concentrations of contaminants in the
supply air to the occupied space could not exceed the specified
values in section 3 of that standard.
The two constraints imposed in those criteria were seldom fol-
lowed, and as a result, the standard'was of ten misinterpreted during
the energy shortages of the 1970s. In 1981, the revised standard
cl arified the recrrculation criteria by providi ng an eq uation w hich
relates a selected filter efficiency to a corresponding recirculation
rate to provide indoor air quality equivaI ent to that expected'by ven-
tilation with 100% outd'oor air [1]:
Vo - Vm
e
where:
l. _
recirculation rate (cfm or 1/s per person).
Outdoor ai r rate speci f'ied i n Tabl e 3 of' ASIIRAR
Standard 62-1981 (cfm or I/s per person).
[1]
The minimum rate of outdoor air that can be used in the
recirculated air ventilating system to provide
acceptable indoor air quality, but never less than 2.5
1/'s (5 cfm) per person.
Efficiency of the contaminant removal (air cleaner)
device. The efficiency should be derived'f rom the most
relevant parameters of the contaminant involved (e.g.,
ppm, or Ing/m3).
This revision addresse6 two short-comings in the previous stand-
ard: 1) it defined the air cleaner efficiency, quantitatively; an62)
i t speci f ied a reci rcul atiom ai r fl ow rate as a functi on of the f il ter
efficiency. In the previous standard, as long as any particulate
f il ter were i ncor porated i nto the sy stem, the amount of outdoor ai r
could be reduced and no ccmpensation in recirculation was specified.

196 FLUID FILTRATION: GAS
i
Thus, common practice was to reduce the total supply air flow rate to
that only required for thermal loads. As energy conservation efforts
were increased, lighting and envelope loads were decreased and'vari-
able air volune systems became popular. As a result, less supply air
was needed for thermal loads and complaints about poor air quality
began to increase. Application of Eq 1 requires the recirculation
rate to compensate- for the reduction in outdoor air, as well as the
air cleaner efficiency. Moreover, it requires the total air supply
rate, Vs (cfm or 1/s per person), to be the sun of the recirculation
and minimun outdoor air flow rates:
llS = Vm + Vr
(21
For exampl e, ASH RAE 62-1981 speci f ies the req ui red' amount of out-
door air for "meeting and waiting spaces" in offices as 17.5 1/s (35
cfm) per person if smoking is allowed'in the space. If it is desired'
to reduce the outdoor ai r fl ew ra te to the mi nimum ot' 3.5 1/s (7 cfm)
per person and to compensate for the smoking by installing air clean-
ers, the required recirculation rate for a system with an air cleaner
efficiency of 100% for "tobacco snoke" ( i. e. , for particulates, gases,
and vapors) would be 17.5 - 3.5 = 14 1/s (35 - 7= 28' efm) per person.
Thus, the total suppl y ai r fl ow rate woul d be 3.5 + 14 = 17.5 1/ s(7 +
28 = 35 cfrn) per persori, the sane as with 100% outduor air, but only
20% of the originally required outdoor air worrld require thermal
treatment. For a more realistic air cleaner efficiency of 50%, the
required recirculation rate would' be 14r'0.5 - 28 L/s (28/0.5 = 56 cfm)
per person, and the required total supply rate wou13 be 28 + 3.5 =
31.5 1/s (56 + 7= 63 cfm) per person. In this case, the thermal load
for the minimua outdoor air would be the sane as for the 100%
efficient air cleaner, but the fan power and space requirements for
the additional recirculation and total air supply rates would' be
significantly larger. Thus, Equations 1 and 2 provide criteria for
evaluating ventilation options which are expected to provide
equivalent indoor air quality.
AIR QUALITY CCNTROL
Equations 1 and 2 do not directly address the quality of the
indoor air. Rather, they provide an indirect procedure to achieve the
same indoor air quality with some recirculation air as would be
expected by ventilating with 100% outdoor air, but the value of that
quality remains unspecified. In ASHRAE Standar662-1981, the indirect
method is known as the "Ventilation Rate Procedure". Another method
is also specified in that standard as the "Indoor Air Quality
Procedure." The latter method specifies objective and'subjective
criteria with which to evaluate the environment, but does not specify
the means to achieve the required control. The Ventilation Rate
Procedure may be considered a prescriptive standard, and the Air
Quality Procedure may be considered a performance standard.
These two procedures may be rel ated by consideri ng a simpl e one
compartment model, Fig. 2. The concentration within this compartment
is a function of the rate of contaminant generation within the

WOODS AND KRAFTHEFER ON OCCUPIED SPACES FILTRA r ION 197
I
I
occupied space, the rate of dilution with outdoor air, the contaminant
concentration of the air transported into the occupied space, and the
rate of removal of the contaminant by the air cleaning system.
Conceptually, this Figure indicates that three methods exist to
control the concentration of a contaminant within the occupied space:
o suppression of the generation rate, or source control;
o reduction of indoor air contaminant concentration by outdoor
air exchange, or dilution control; and
o removal of indoor air contaminant concentration by air
cleaners, or removal control. '
BLOVIER
V~
Co
N NET
DILUTION Vo, GENERATION. CI V.
RATE 4 RATE f
~
c. ICa' 11,e) Ca L_j CI' C.,
OCCU~IEDSPACE ' I AIRCLEANER.
E V't C.
REMOVAL
RATE
In steady-state within a well-mixed space, a relationship among
these three control methods may be expressed as:
N F
<
Figure 2. One compartment, unif ormly mixed, steady-state model
for indoor ai r quality.
[3)
AC =
where: ! C = Ci;
the difference between the uniformly mixed
indoor air concentration, C, and the outdoor
air concentration, Co (tlg/r3) .
N= Q- S= the net generation rate of,the contaminant in
the occupied space, where Q is the source
strength ( i. e. , emission rate) and S is the
sink strength (i.e., settling or sorption rate),
(tig/hr) .
E = VreCu =
the removal, rate of a contaminant in the air
cleaner (lig/fir); where Vr is th recirculation
rate through the air cleaner (m~/hr), e is the
efficiency of the air cleaner rated in terms of
the contami nant removed ( i. e. , s= 1 - Cd/CU) ,
Cu is the contaminant concentration upstream of
the air cleaner (i.e., Cu = Ci for a well-mixed
system), and Cd is the contaminant concen-
tration downstream of the ai:r cleaner.
ou door air fl ow rate f or dilution control
(m~/hr).

198 FLUID FILTRATION: GAS
In this model, the diiution rate, Vo, represents inf il tration,
natural ventilation, or mechanical ventilation with outdoor air. The
removal rate, E, represents the rate at which ttre contaminant is ac-
cunulated in the air cleaner. For the simple case in this model, the
removal rate ( i. e. , E= VrECu could be achieved by fan-fil ter mod-
ules now aviilable as c:rnsunrzr products, or by filtered recirculated
air commonly used in residential forced air systems. Note that the
removal rate is a function of three factors. Thus, for a given up-
strean concentration, the sane rernoval rate can be expected fran two
devices; one which has an air cleaner efficiency of' one-half the other
if its recirculation rate is twice the other's. Moreover, as the in-
door concentration decreases ( i. e. , Cl, and Cu approach zero) , the
removal rate of a device with a fixed product of IrE decreases.
For the case where the air cleaner is located in the mixed air,
Fig. 1, the rel ationship among the three control methods may still be
expressed by Eq 3, but the removal rate must be defined as E_(VoCo +
VrCr)e. The advantage of this configuration is that contaminated
outdoor air is also treated by the air cleaner before it enters the
occupied space. This feature is especially important when it is
necessary to control the indoor air concentration belaw that of the
outdoor air.
Although Eq 3 was derived fran a simple model, it serves to ident-
ify sane basic control strategies and' their limitations t'or indoor air
qual,ity control!:
o If removal controli is not employed~ (i.e., E= 0), the indoor
concentration will exceed,the outdoor concentration urrless the
source is removed ( i. e. , N= 0) or an inf ini te dilutiurn rate is
provided (i.e., Vo = -).
o If the outdoor concentration is to be controlled belar that of'
the outdoor air and the dilution rate is finite,.the removal
rate must exceed the rret generatiore rate (i.e., E) N)l
o Outdoor air required for dilution contrul may be reduced with-
out affectiing AC, if' the difference betweera the net eerierati<rn
rate and the ru,roval rate is corre::{,und'int;ly rcducecJ.
o To achieve an acceptable ,~C econanically, a cuutiirred strateCy
of sourcu, r(srroval, arid dilution contrci probably will t,e re-
quired.
ACCEPTABILITY CRITERIA
Only source control' canieliminate occupant exposure to a cunl.ar.,r-
nant; dilution and removal cor,trol require mixture cf the currtan.irurnt
within the occupiled space before their mechaudisms N.:cume roefrtl. Thrr~,
both of these control methods expose occupants lo ttre cuntansiro rits,
arid stwrui d only be used ii' some 1 evel of exE,osur-e i s"acce{,taLl e".
Air quality may be defirred, getierally, as "the nature of air lhatt
affects your health arid well-being". In Uiisdet iniliun, the Wvr1cI
Health Urganization's concept of healthi is imt,lied: "He«lU1, is a: :.tatc
of compiete physical, mental and social weil-beira;, and! nut rucrtly the

WOODS AND KRAFTHEFER ON OCCUPIED SPACES FILTRATION 199
absence of disease or infirmity" [6]. These definitions offer criteria
for evaluating beneficial, as well as deleterious effects of indoor
environments. However, use of these definitions to ascertain accept-
able indoor air quality requires both objective and subjective cri-
teria. Objective criteria may be expressed as quantitative values of
environnental stress which result in measurable physiological or psy-
chological (i.e., behavioral) strains on the occupants. Thus, these
criteria may be used to ascertain compliance with environmental con-
ditions that should not cause measurable disease, disability, or
dysfunction. Subjective criteria may be expressed in terms of af-
fective responses of the occupants (e.g., comfort, annoyance, dis-
comfort). When stress results in a complete state of well-being, a
comfortable (:i.e., healthy) strain may exist. The amount of deviation
frcm these ideal conditions that can be accepted without discomfort or
adverse health effects is d'ependent upon the occupant's abilities to
adapt to the deviations. As the ability to adapt diminishes, sus-
ceptibility to the adverse effects of the stress increases. Thus,
susceptible populations within occupied spaces must be considered when
"acceptable ranges" of environmental stressors are selected.
Traditionally, ASIIRAE has defined'acceptable environments as those
in whictr 80% of the occupants find satisfactory:
o Acceptable air quality is defined as "air in which there are no
known contaminants at harmful concentrations and with which a
substantial majority (usually 80%) of the people exposed do not
express dissatisfaction" (1].
o Acce table thermal environment is defined as "an envirorment in
which at least 80% of the occupants would fin6thermaily ac-
ceptable" [7].
For purposes of evaluating control strategies, a more technical
def'inition of indoor air quality has been proposed which incorporates
the above concepts [8]:
The quality of the air iman enclosed space is an indicator of haw
we1L the air satisfies three criteria:
o Thermal conditions of the air must be adequate to provide ther-
mal acceptability for the occupants as defined by ASHRAE Stand-
ard 55-1981.
o The concentrations of oxygen and carbon dioxide must be within
acceptable ranges to allow normal functioning of the respir-
atory system.
o The concentration of gases, vapors, and particulates should be
below lievels that can have deleterious effects, or that can be
perceived as objectionable by the occupants.
This definition addresses three important factors needed to
achieve acceptable indoor air quality control. First, it recognizes
that ai r quali ty cc:~ntrol should be considered to be integral wi th con-
trol of We thermal environment. While some aspects of source control
can be achieved without reliance on thermal control (e.g., product
substitution)~, suppression of tlie net generation rate by contairment

200' FLUID FILTRATION: GAS
or isolation requires interface with the thennodynamic state of the
air in the occupied space. Moreover, neither dilution nor removal
control can be achieved without control of air movement, a thenno-
dynamic process. Second, it suggests that responses to indoor air
quality can be quantified in tenns of a subjective scale, not unlike
those for predicted mean vote (PMV), percent people dissatisfied (PPD)
or standard effective temperature (SEM [9, 10]. Third, and maybe
most important, it implies that simultaneous control of the three
methods is required, if satisfactory responses are to be achieved.
IMPROUED CONTROL STRATE1jIES
A classical conflict has developed between concepts of energy con-
servation and environmental acceptability. During the energy crises
of the last. decade, ventilation systems were de-activated, building
envelopes were "tightened", and temperatures and relative humidities
were allowed to decrease in winter and increase in summer. As a re-
sult, environmental quality was degraded, sometimes to the extend that
the health of occupants was jeopardized. Terms tc describe these con-
ditions are now in literature, such as "Sick Building Syndrome",
"Tight Building Syndrome", and "Building Related Illness" [11]. Con-
versely, data also indicate that this conflict need not exist. Rather,
if environmental control i's approached intelligently, energy efficient
operation will result (12, 133.
/A4
Figure 3. System schematic for micro- and mini-environmental,
closed-loop control for thermal and air quality acceptability.

WOODS AND KRAFTHEFER ON OCCUPIED SPACES FILTRATION 201
A composite of these control strategies is shown schematically in
Fig. 3. In this Figure, the region of primary concern within the room
(i.e., micro-envi'ronment is shown as Compartment 1, and the remainder
of the robm (i.e., mini-environment) is shown as Compartment 2. The
relationship between the mini- and micro-environments is represented
by a filtered room-air supply (1 - E 1)m2, and a room-coupling co-
effi'cient, a, a factor which is similar to the concept of "Venti-
lation Efficiency" (12, 14).
Roan Ventilation Control
The thermal and air quality control interaction between the HVAC
system and the mini-environment can be expressed in terms of the fol-
lowing steady-state equations:
o The mass balance of the contaminant in the mini-environment:
msxs + mixo + Nx2 = (ms + mi)x2
(4)
where:
m = mass air flow rate (gdry air/hr)
C
Nx2 = the generation rate of the contaminant i'n the mini-
env i ronment.
x = mass concentration of contaminant (Ngcont./gdry air)
o The fraction of mini-environmental supply air flow to system
air flow:
z = ms/mm
[5]
o'Ihe mass balance of the contaminant in the tN AC system, down-
stream fran the air cleaner:'
%xm(1 - E2) + Ns = rt4nxs
where Ns is the generation rate of the contaminant in the
IIVAC system, downstream fran the air cleaner which has an
efficiency of L2. (ugcont./hr).
[6]
o Itie mass balance of the air in the mixed air system:
mo + mr = mm
171
o The mass balance of the contaminant in the mixed air system:
moxo + mrxr = R4nxm
[8l
o And the energy balance of the mixed air system in terms of
specific enthalpy, h (J/gdry air):
rtb1k) + mrli~ = mnh4n
[9]

202 FLUID FILTRATION: GAS
In tfiese equations, the subscripts represent:
i= infiltration and natural ventilation rates into the mini-
environment (i.e., psychrometric condition 5 in Fig. 3).
m.= mixed air in HVAC system (i.e., psychrometric condition 6 in
Fig. 3).
o- outdoor ai r( i. e. , psychrometric condi tion 5 in Fi g. 3).
r= recirculated air into"fNAC system ( i. e., psychrometric condi-
tion 4 in Fig. 3).
s- supply air to mini-environment ( i. e. , psychrometric condition
8 in Fig. 3).
Note that it is necessary to express these balances in terms of
mass flow rates of "dry air" rather than volumetric rates, as iso-
thermal conditions can no longer be assumed'and changes in air den-
si'ties must be considered due to the psychrometric processes.
Equations 4 through 9 may be combined to provide an expression for
the "Room Acceptability Ratio," K2, defined as the ratio of roan air
to outdoor air contaminant concentrations:
x2 (H + (1 - H)x /x )(1 - E ) + M + p_
fC2= = r o 2 2
[10]
x 1 + M
0
where:
H= mo/m~ _( hr - h~)/( hr - ho)
[11]
M = mi/ zmm [12]
Q
= W zrt
x (13)
2
o
M
where:
N=zNs+ Nx2
If the contaminant concentration in the mini-envirorment is identical
to that in the recirculated' air (i.e., x2 = xr), Eq 10 simplifies to:
K2_ x2 - H(1 - e2 ) + M + Q2 [14']
xo H(1 - e2) + M+12
Functional relationships from Fq 14 are shown in Figures 4-7 be-
tween the "Roan Acceptabili'ty Ratio," K2 ( i. e., x2/xo), and the "Room
Contamination Factor," Q2, with the "Air Cleaner Efficiency," e-2, the
"Passive to Active Air Exchange Ration " M, and the "Outdoor Air
Ratio," H, as parameters. In each of Ehese Figures, four sets of
graphs are presented for air cleaner efficiencies at 0, 0.2, 0.5, 0.9,
at each of four outdoor air ratios of 0.2, 0.5, 0.75, and 1.0. Also
shown in each set of graphs is the reference condition of =2 = 1.0,
