Evaluation of A Vertical Displacement Ventilation System
Fields
- Author
- Holbrook, G.T.
- Koganei, M.
- Olesen, B.W.
- Seelen, J.
- Woods, J.E.
- Koganei, M.
- Type
- PSCI, PUBLICATION SCIENTIFIC
- ABST, ABSTRACT
- BIBL, BIBLIOGRAPHY
- CHAR, CHART, GRAPH, TABLE, MAPS
- DRAW, DRAWING
- ABST, ABSTRACT
- Area
- CENTRAL FILES/PRE-DB WAREHOUSE
- Document File
- 2021578674/2021578937/Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control
- Litigation
- Ppla/Produced
- Characteristic
- EXTR, EXTRA
- Site
- R107
- Named Organization
- Asahi Kogyosha
- Va Polytechnic Inst + State Univ
- Author (Organization)
- Asahi Kogyosha
- Proceedings of Indoor Air 93 Vol 5
- Va Polytechnic Inst + State Univ
- Proceedings of Indoor Air 93 Vol 5
- Named Person
- Koganei, M.
- Master ID
- 2021578685/8936
Related Documents:- 2021578685-8936 Period 2 Project Report Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control 920516 to 930831
- 2021578705-8708 Comparative Evaluation of Displacement Ventilation and Conventional Vav Systems for Indoor Air Quality Control
- 2021578709
- 2021578711-8717 Proposal to Philip Morris, Usa for Continuation of Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control
- 2021578719-8753 Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control Status Report: Design Process of the Research and Demonstration Facility Phase II
- 2021578755-8762 Indoor Environment Program Meeting with the Science Advisory Committee 930129 Minutes and Action Items
- 2021578764-8780 Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control Progress Report 920515 - 921115
- 2021578781-8785 Appendix A Abstracts for Indoor Air '93
- 2021578786-8790 Appendix B Project Overview Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control
- 2021578791-8798 Appendix C Performance Criteria
- 2021578800-8815 Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control Progress Report 921116 - 930215
- 2021578816-8824 Appendix A Minutes of the 930129 Science Advisory Committee Meeting
- 2021578825-8831 Appendix B Rational Building Performance and Prescriptive Criteria for Improved Indoor Environmental Quality
- 2021578832-8838 Appendix C Modeling the Thermal and Indoor Air Quality Performance of Vertical Displacement Ventilation Systems
- 2021578839-8845 Appendix D Evaluation of A Vertical Displacement Ventilation System
- 2021578847-8855 Design and Construction of A Facility for Research and Demonstration of Healthy Building Concepts
- 2021578856 Indoor Air '93 Proceedings of the 6th International Conference on Indoor Air Quality and Climate Volume 3. Combustion Products, Risk Assessment, Policies
- 2021578857-8862 Rational Building Performance and Prescriptive Criteria for Improved Indoor Environmental Quality
- 2021578863 Modeling the Thermal and Indoor Air Quality Performance of Vertical Displacement Ventilation Systems
- 2021578864 Indoor Air '93 Proceedings of the 6th International Conference on Indoor Air Quality and Climate Volume 5. Ventilation
- 2021578865-8870 Modeling the Thermal and Indoor Air Quality Performance of Vertical Displacement Ventilation Systems
- 2021578871 Evaluation of A Vertical Displacement Ventilation System
- 2021578872 Indoor Air '93 Proceedings of the 6th International Conference on Indoor Air Quality and Climate Volume 5. Ventilation
- 2021578879 A Characterization of Methodologies for Assessing Human Responses to the Indoor Environment
- 2021578880 Indoor Air '93 Proceedings of the 6th International Conference on Indoor Air Quality and Climate Volume 1. Health Effects
- 2021578881-8886 A Characterization of Methodologies for Assessing Human Responses to the Indoor Environment
- 2021578887-8897 A Case Study: Cost Implications for Hvac Commissioning
- 2021578898-8903 Appendix A Specification Section 15995: Commissioning of Hvac System Contract Specifications for Architecture Research and Demonstration Facility Phase II, Virginia Polytechnic Institute and State University, College of Architecture and Urban Studies, Blacksburg Virginia, Rev. 11 930800
- 2021578905 Fluid Filtration: Gas Volume I A Symposium Sponsored by Astm Committee F-21 on Filtration and the American Program Committee of the Filtration Society Philadelphia, Pa, 861020 - 861022
- 2021578906-8926 Filtration As A Method for Air Quality Control in Occupied Spaces
- 2021578927 Indoor Air Volume 5 Buildings, Ventilation and Thermal Climate
- 2021578928-8932
- 2021578934-8936 Economic Modeling of Vav and Vdv Systems in Rdf II
- Date Loaded
- 07 Jan 1999
- UCSF Legacy ID
- ykc33e00
Document Images
ProccCdings of Indoor Air '93,, Vol. 5
L'VALUATION OF A VE'RTICAL DISPLACEMENT VENTILATION
SYSTEM
265
f3jarne W. Olesen', Makoto Koganei2, G. Thomas Iiolbnook', Julie Seelen' and James E.
woXxis'
'lndoor Environment Program, Virginia Polytechnic Institute and State University, USA
ZRe.search and 1)evelolnnent Center, Asahi' Kogyoslia Co., Japan
AIISTRACT
The effectiveness of a vertical displacement ventilation system was evaluated when
contaminants including tobacco smoke were present. The system tested supplied air
through a perforated floor and carpet. 'lhe system performance was evaluated using ADPI,
percentage dissatisfied due to draught, vertical temperature profile, air change
effectiveness, and contaminan[ removal effectiveness. Gaseous contaminants were
simulated with tracer gas. Also, particulates, CO, and CO2 were generated by cigarettes
and occupants. Several combinations of supply air flow rate and thermal loads in the
occupied zone were evalua(ed. Because of the method of air supply, very uniform air
temperature and velocity conditions were obtained. '11ie risk of draught was fonnd to be
negligible. 'I1ie air change effectiveness of the system varied from 130 to 200%.,
increasing with increasing supply air flow rate and decreasing with increasing thermal load
in the space. C.ontaminant removal effectiveness was less dependent on the siihply air
flow rate and thermal loads than the air change effectiveness and varied, depending on
type of contaminant, frrnai 80 to 580%.
IN"1'RUI)UC'I'1ON
The cause for many cases of Sick Building Syndrome is poor ventilation due to either
inadequate flow of outdoor air or Poor distribution of the air in the system or in the
occupied space. '1 he distribution of the air influences both the thermal conditions and the
indoor air quality in the space. '17ie quality of the thermal environment is affected by the
air temperature unifonnity in the occupied space, i.e. vertical air temperature differences,
and risk for draught. Draught sensation is the combined effect of air temperature, mean air
velocity, and turbulence intensity. Indoor air quality is influenced by the quality of the
suhply air, the emission rates of sources in the space, the degree of contaminant dilution in
the space, and the degree of contaminant removal from the occupied space.
Ihe requirements for the amounC of outdoor air or the air change rates listed in existing
standards and codes (1,2) assume complete mixing of the air in the ventilated space. Since
comt;lete mixing does not always occur, it is necessary to take into account how efficiently
the air is distributed in the occupied zone. In the case where there are zones of stagnant
air a:,d/or short circuiting, it utay be necessary to increase the amount of outdoor air
required by code and the total supply air flow rate. In the case of displacement flow, the
amount of outdoor air required by code may be reduced. To properly assess the
ventilation in the breathing zone, one must determine: ( l) The air renewal/air distribution

rncccc ings cd Inctoor Air 93. Vot. 5
process: llow quickly "old" air is replaced with "new" air in the occupied zone: and
(2) The contatninant removal process: llow effectively contaminants generated in dte space
are removed from the space and prevented from spreading in the occupied zone. These
two processes are related but not identical and therefore need to be treated separately. For
both air renewal and contaminant removal it is important to distinguish between results
based on room average, occupied zone average or local conditions. Complete mixing here
is referred to as having an air change effectiveness of 1UO%.
The objective of this study is to evaluate the perfonnance of a vertical displacement
ventilation system with air supply through a perforated floor. Initial results of this
evaluation and a discussion of the measurement of air change effectiveness and
contaminant removal effectiveness are presented. Data were obtained for several
cozitaminants, two different supply air flow rates, and two therrnal load conditions.
R1F;1'11OUS
Tests were performed in a test room with aimost adiabatic walls and ceiling, served by a
vertical displacement ventilation system supplying air through a perforated floor/carpet and
returning air through grilles in the ceiling (Figure 1). All tests used l(H)% outside air, i.e.,
no return air was recirculated. Before the start of the tests the supply and exhaust air
flows were balanced. Thermal loads consisted of fluorescent lights (total of 240 W, wall
mounted near the ceiling) and five persons who were simulated by electric blankets. These
blankets were folded so the surface area was similar to that of a standard person. The
output wattage, for each blanket (120 W), was determined from its electrical resistance at
operating conditions. Supply air flow rates were 142 and 472 Vs and thermal load levels
were 14 and 44 W/tn2. Gaseous contaminants were simulated with tracer gas (SFJ, dosed
in the center of the room at 0.9 in. Particulates and CO were generated by 6 burning
cigarettes also at 0.9 in. CO2 was generated by one person sitting in the center of the
room (breathing level at 1.1 in). Total Volatile Organic Compounds (TVOC) were
generated by both cigarettes and occupants. When the person was in the roorn, the thermal
load output of the blanket in the center was reduced to 50 W.
O
O
O
cb3ir
0
O aT
0
chair chair
chair
0
0 measwement
location
(a) Room plan with tobacco smoke dosing
at "T" and tracer gas dosing at "S".
f-
t
remrn
air
7
grilles
,2,Sm---------------
1,7m--- supply
`/ 1'1m----- - - - - ----
~
0.1 m 0.6m
`- perforated Ooar/carpiet ~
suppl y
I
JJ
(b) Room section with measurement heights
annotated.
Figure I. Schematic of test room.

t'rocccdings of tndoor Air '')3. Vol. 5 267
The thernnal environnre+rt in the occupied zone was evaluated measuring air velocity (3
min. mean and standard deviation), and air temperatures at four heights (0.1 m, 0.6 in, 1.1
m, 1.7 m) and at four locations (Figure 1). From these measurements ADPI, vertical air
temperature differences, and percentage dissatisfied due to draft (PD) were calculated
(3,4,5). ADPI was calculated as the percentage of points meeting the criteria:
-L7 °C < 0 < 1.1 °C, where 0 = t, - t.. - 8 (v. - 0. 15) (1)
where: 9= effective draught temperature (°C); t,a = average test zone air
temperature (°C); t, = corrected air temperature (°C); v, = mean air velocity (rn/s).
The percentage of dissatisfied due to draught (PD) was calculated with:
PD=( 34-t)(v,-0.05)062(0.37SD+3:14) (2)
where: SD,, = Standard deviation of air velocity.
The air change effectiveness of the ventilation system was calculated by dividing the local
age-of-air in the return by the local age-of-air at 1.1 m height in the center of the room.
The age-of-air in a point in the room is a measure of the time it takes the supply air to
reach that location in the room (6,7). The local age-of-air in the center of the room at 1.1
m (breathing level of a sedentary person) was selected to represent the breathing level of
the entire room. The age-of-air was measured using the step-up method dosing tracer gas
(SF6) in the supply duct, as described by Sutcliffe (8).
Contaminant removal effectiveness, t:`, is a measure of how effectively contaminants
generated in the space are removed from the space and prevented from spreading in the
occupied zone, calculated as in (9):
t:`=(C, -C,)/(C,-C,) 100% (3)
where: C, = contaminant concentration in the extract (return) air; C, = contaminant
concentration in the supply air; C, = average contaminant concentration in the space.
Gaseous contaminants were measured with the photo-acoustic detection method, and
particulates with the piezo-balance method.
RESULTS ANI) DISCUSSION
The therrnal environnient was very uniform (Table 1). Vertical temperature differences
were less than l.0°C between ankle (0.1 m) and head (1.1 m) for a sedentary person and
less than 1.5°C for a standing person (0.1 m and 1.7 m). Mean air velocities were always
lower than 0.10 m/s in die occupied zone and for most locations about 0.05 rn/s. The
AS(1RAE-113 recommends that ADPI should be more than 809'0. When the system was
operated at the higher air flow, the index dropped to 65%. Since the measured air
velocities in most cases were about 0.05 m/s, the corrected air temperature due to air
velocity, calculated as -8 (v, - 0.15 m/s), was +0.8°C. Since the limiting effective draught
temperature is 1.1 °C, the maximum acceptable difference between the test point
temperature and the average zone temperature is then only 0.3°C. ADPI calculation

268
Proceedings of Indoor Air'93: voli 5
implies that the optimal air velocity is 0.15 m/s, but it has been demonstrated that at 0. 15
m/s people may experience draft (4,10). The data for the percentage dissatisfied due to
draught show that all points in the occupied zone were lower than the 15 % recommended
in ISO/DIS 7730 and ASHRAE 55-92. This indicates that, in this case, the criteria used
for ADPI do not give a correct evaluation of the impact that the air velocity distribution
may have on comfort. Thus, it is recommended that these criteria be modified for
consistency with the ISO/DIS 7730 and ASHRAE 55-92 standards.
Table 1. ADPI, Percentage Dissatisfied due to draught (percentage of points where
PD < 15 % and average PD), an& Air Change Effectiveness (ACE) for two different supply
rates and two thermal load conditions.
d
L Supply rate 142 I/s (300 cfm) Supply rate 472 l/s (1000 cfm)
oa
W/mz ADP PD < 15 PD avg ACE ADP PD < 15 pD avg ACE
I % I %
1'3 100 100% 0.7% 130% - - - 180% ~
44' 94% 100% 0.3% 146%' 65% 100% 1.6% 200%
The test was interrupted, there ore tht's value needs to be ven ted wtth urther testtng.
The air change effectiveness was always higher than 100% and increased with higher
supply air flow rate (Table 1). At the higher supply flow rate, the air change
effectiveness was about 200%. Theoretically, the maximum air change effectiveness for
piston flow is 200%, based on the average age-of air of the space measured at half the
room height. Since for this study, the effectiveness was based' on the local age-of-air
measured at one third' the room height (1.1 m level), the resulting air change effectiveness
woui6 be around 300% at complete piston flow. Increasing the thermal load to 44 W/m2
increased the air change effectiveness a little. With the limited amount of data this
difference is probably not signifigant.
The contaminant removal effectiveness is influenced by the supply flow rate, by the
thermal loads, and by the type of source. For the higher air flow rate, the contaminant
removal effectiveness was higher for all contaminants except CO2, ranging from 200 to
500% - significantly higher than for complete mixing, i.e.,, 100%. C02, generated' by the
person sitting in the room, was emitted with a lateral impulse as opposed to the other
contaminants which had a negligible initial velocity. Therefore the contaminant removal
effectiveness for C02 was not significantly influenced' by the supply flow rate or thermal:
loads but mainly dominated' by the fact that it had an initial velocity. The removal
effectiveness was below 100% only for the gaseous contaminants (SF6) in the case of low
supply rate and high thermal load. This was because the SF6 is a "cold" source, its
density is greater than air causing the SF6 to miz with the air below the dosing point, and
also because in this study it was dosed above an electric blanket. For the low thermal
condition, the blanket was turned off, t;o thermal flow was provided, an& SF6 spread in all
directions resulting in low local concentrations. For the high thermal condition, the
blanket underneath the dosing point was turned on, providing a thermal flow upward,
taking the SF6 upward in its plume, resulting in higher concentrations. The cigarettes ar°
"warm" sources, although they do not ~ignificantly influence the heat load in the room,
they influence the local thermal conditions because of their small heat plumes. These heat
plumes take the generated contaminants upwards. See concentration profiles for C0,
TVOC, and particulates in Figure 2.

Procccdings of Indoor Air '93, Vol. 5
Table 2. Contaminant Removal Effectiveness (CRE) for different contaminants and for
two different supply rates and two thermal load conditions.
269
Conta- Load CRE (%); supply rate 142 Vs CRE (%); supply rate 472 I/s
minant WJm, 1.1 m 1.7 m average 1. 1 m 1.7 m average
13 216 188 201 - - -
C02
44
217
112
204
176
106
213
13 259 237 241 - - -
CO
44
382
241
315
392
451
582
13 363 374 364 - - -
TVOC 44 340 238 297 372 404 534
13 219 219 241 - - -
S F6
44
92
81
133
403
220
411
Parti- 13 323 - - - - -
culate 44 298 - - 461 - -
Contaminant Symbol
C02
CO
TVOC
SF6
Particulate
3.2
0
(142 U.)
(Ce Cs)
106ppm
(472 V:)
(Ce, Cs)
32.9ppm
0 8.85ppm 2.98ppm
A 4.57ppm I.74ppm
O 5.30ppm 1.84ppm
0
0.68mg/mj 0.26mg/m3
3.2
0.0 F .lu 1 1t Ldu I I l 0.0
0.0 0.5 1.0 1.5 0.0 0.5 1.0 1.5 0.00 0.03 0.06 0.09
(C,-C)/(C,-C) (C,-C)l(C,-C) Velocity, m/s
Figure 2. Normalized profiles of local concentrations (C,) and velocities averaged over
four locations in test room at 44 W/m' and at two supply flow rates. Tite normalized
profiles are equivalent to the inverse of the local contaminant removal effectiveness.
Open symbols for 142 I/s,
solid symbols for 472 I/s.

270
t'roccedings of Indoor Air '93, Vol. 5
The problem with obtaining meaningful contaminant removal data is determining the
proper sampling locations to arrive at a representative data set. The contaminant
concentration can be measured at one height, e.g., breathing level, or averaged over a
volume, e.g., the entire occupied zone. Also the distance from the source to sample
locations should be taken into account as well as the source temperature and type of
contaminant. Until a standard methodology is developed, the sample locations utilized to
characterize the room or zone of interest, and the source and its contaminants should be
included when presenting contaminant removal effectiveness data.
CONCLUSION
Even though the data reported here are limited and the tests must be repeated to obtain
statistically significant results, it is clear that the performance of a displacement ventilation
system does not depend solely on the system itself. Other factors such as the thermal
load condition, the total supply rate, and the type and location of the contaminant
generated in the room to play important roles in determining the overall system
performance.
Criteria used in determining the ADPI must be reviewed to reflect results on peoples'
perception of draught. The definition and measurement method for contaminant removal
effectiveness needs to be further detailed.
ACKNUWLEU(.I?MEN"f
We are pleased to acknowledge that this study is being funded by Philip Morris USA.
We also gratefully acknowledge the support from Asahi Kogyosha Co., Ltd. for Dr.
Koganci as a Visiting Scholar at the Virginia Tech Indoor Environment Program.
REFI;RI;NCi;S
1. ASIIRAE. Std. 62-89: Ventilation for Acceptable Indoor Air Quality. Atlanta, 1989
2. EEC Report No. 11. Guidelines for Ventilation Requirements in Buildings.
3. European Concerted Action (COST-fi 13). Commission of the European
Communities, Luxernbourg, 1992.
ASFIRAE. Std. 113-90:' Method of Testing for Room Air Diffusion. Atlanta, 1990.
4. ASIIRAE. Std. 55-92: Thermal Environmental Conditions for Ilutnan Occupancy.
5. Atlanta, 1992.
ISO 7730. Moderate thermal environments - Determination of the PMV and PPD
indices and specification of the conditions for thermal comfort. International
Standards Organization, Geneva, 1984. Revised: 1993.
~
6. Sandberg M, Sjoberg M. The use of movements for assessing air quality in N
ventilation rooms. Buildings and Env., 1983;18:181-197. ~
7. Skaaret E, Mathisen tIM. Ventilation Efficiency. Env. Int: 19P2:8 N
8. Sutcliffe 11. Technical Note No. 28: A Guide to Air Change Efficiency. AIVC, UK, ~
1990. ~
9. Brouns C, Waters B. Technical Note No. 28-2: A Guide to Contaminant Removal ~
Effectiveness. AIVC, UK, 1991. ~
10. Fanger PO, Melikow AK, Ilanzawa 11, Ring J. Air turbulence and sensation of
draught. Energy and Buildings 1988;12: #1.