Philip Morris
Modeling the Thermal and Indoor Air Quality Performance of Vertical Displacement Ventilation Systems
Fields
- Author
- Holbrook, G.T.
- Koganei, M.
- Olesen, B.W.
- Woods, J.E.
- Type
- PSCI, PUBLICATION SCIENTIFIC
- ABST, ABSTRACT
- BIBL, BIBLIOGRAPHY
- CHAR, CHART, GRAPH, TABLE, MAPS
- DRAW, DRAWING
- Area
- CENTRAL FILES/PRE-DB WAREHOUSE
- Document File
- 2021578674/2021578937/Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control
- Litigation
- Ppla/Produced
- Characteristic
- EXTR, EXTRA
- Site
- R107
- Named Organization
- Asahi Kogyosha
- Va Polytechnic Inst + State Univ
- Author (Organization)
- Asahi Kogyosha
- Proceedings of Indoor Air 93 Vol 5
- Va Polytechnic Inst + State Univ
- Named Person
- Koganei, M.
- Master ID
- 2021578685/8936
- 2021578685-8936 Period 2 Project Report Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control 920516 to 930831
- 2021578705-8708 Comparative Evaluation of Displacement Ventilation and Conventional Vav Systems for Indoor Air Quality Control
- 2021578709
- 2021578711-8717 Proposal to Philip Morris, Usa for Continuation of Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control
- 2021578719-8753 Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control Status Report: Design Process of the Research and Demonstration Facility Phase II
- 2021578755-8762 Indoor Environment Program Meeting with the Science Advisory Committee 930129 Minutes and Action Items
- 2021578764-8780 Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control Progress Report 920515 - 921115
- 2021578781-8785 Appendix A Abstracts for Indoor Air '93
- 2021578786-8790 Appendix B Project Overview Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control
- 2021578791-8798 Appendix C Performance Criteria
- 2021578800-8815 Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control Progress Report 921116 - 930215
- 2021578816-8824 Appendix A Minutes of the 930129 Science Advisory Committee Meeting
- 2021578825-8831 Appendix B Rational Building Performance and Prescriptive Criteria for Improved Indoor Environmental Quality
- 2021578832-8838 Appendix C Modeling the Thermal and Indoor Air Quality Performance of Vertical Displacement Ventilation Systems
- 2021578839-8845 Appendix D Evaluation of A Vertical Displacement Ventilation System
- 2021578847-8855 Design and Construction of A Facility for Research and Demonstration of Healthy Building Concepts
- 2021578856 Indoor Air '93 Proceedings of the 6th International Conference on Indoor Air Quality and Climate Volume 3. Combustion Products, Risk Assessment, Policies
- 2021578857-8862 Rational Building Performance and Prescriptive Criteria for Improved Indoor Environmental Quality
- 2021578863 Modeling the Thermal and Indoor Air Quality Performance of Vertical Displacement Ventilation Systems
- 2021578864 Indoor Air '93 Proceedings of the 6th International Conference on Indoor Air Quality and Climate Volume 5. Ventilation
- 2021578871 Evaluation of A Vertical Displacement Ventilation System
- 2021578872 Indoor Air '93 Proceedings of the 6th International Conference on Indoor Air Quality and Climate Volume 5. Ventilation
- 2021578873-8878 Evaluation of A Vertical Displacement Ventilation System
- 2021578879 A Characterization of Methodologies for Assessing Human Responses to the Indoor Environment
- 2021578880 Indoor Air '93 Proceedings of the 6th International Conference on Indoor Air Quality and Climate Volume 1. Health Effects
- 2021578881-8886 A Characterization of Methodologies for Assessing Human Responses to the Indoor Environment
- 2021578887-8897 A Case Study: Cost Implications for Hvac Commissioning
- 2021578898-8903 Appendix A Specification Section 15995: Commissioning of Hvac System Contract Specifications for Architecture Research and Demonstration Facility Phase II, Virginia Polytechnic Institute and State University, College of Architecture and Urban Studies, Blacksburg Virginia, Rev. 11 930800
- 2021578905 Fluid Filtration: Gas Volume I A Symposium Sponsored by Astm Committee F-21 on Filtration and the American Program Committee of the Filtration Society Philadelphia, Pa, 861020 - 861022
- 2021578906-8926 Filtration As A Method for Air Quality Control in Occupied Spaces
- 2021578927 Indoor Air Volume 5 Buildings, Ventilation and Thermal Climate
- 2021578928-8932
- 2021578934-8936 Economic Modeling of Vav and Vdv Systems in Rdf II
Related Documents:
Document Images
i'roccalungs «I Inuoor rXir Yj. Vol. 3
MODI?LINC 'I'111; TIl1;RMAL ANE) INI)OOR AIR QUALITY
I'1?RhnRMANCt: O1~ VI:R'I'ICAL DISPLACL'MI;NT VE:N'I'ILA'1'InN
SYSTEMS
Makoto Koganeit, G. Thomas Ilolbrook2, Bjarne W. Olesen2, James E. Woods2
tResearch & Development Center, Asahi Kogyosha Co., Ltd., Japan
2lndoor Environment Program, College of Architecture and Urban Studies, Virginia
Polytechnic Institute and State University, USA
AI3S'I'RACT
To predict the thermal and indoor air quality performance of vertical displacement
ventilation systems using two-zone modeling, it is necessary to account for the different
nature of the air flow due to thermal and contaminant mixing within these zones. Two
zone modeling of vertical displacernent ventilation was performed assuming piston flow in
the clean zone, uniform mixing in the dirty zone, and no recirculation between the zones
except via heat source plumes. The resulting equations for air change effectiveness and
contaminant removal effectiveness more closely match observed vertical displacement
ventilation performance than previous studies, especially under non-isothermal conditions
with heat sources.
IN'1'RODU(:TION
Previous experiments with a vertical displacement ventilation system performed in a
2.8m x 2.6m x 3m test room during early summer and winter show that a room with heat
loads (3Q-17t) WImZ) is divided into two zones: a lower, "clean" (unmixcd); zone with
temperature stratification connected by heat source plumes to an upper, "dirty" (mixed)
zone with an almost uniform temperature distribution (1). Contaminants added to the
upper zone mix with the turbulent air flow in that zone while contaminants added to the
lower zone do not mix but, ascend until entrained by heat source plumes. Past attempts to
mathematically model vertical displacement ventilation systems have not fully accounted
for the different nature of the air flow and temperature distributions within the upper and
lower zones (2, 3). `Ilrese models have typically assumed uniform temperatures and
contaminant mixing within each zone, and a recirculation factor applied between the two
zones. For these models, air change effectiveness and contaminant removal effectiveness
can only be evaluated for a specified recirculation factor and clean zone height, both of ~
which are not easily quantified for a given room condition. Tlte effects of internal heat ~
loads and temperature stratification on air flow patterns and the resulting air quality have PA
not been accounted for in these models. CA
Results described herein, indicate that modeling a vertical displacement ventilation system ~C~
is improved by assuming: 1) piston flow in the clean zone and uniform mixing in the dirtyQ7
zone; 2) no recirculation between zones except via heat source plumes; 3) that the clean ~
zone height can be expressed as a function of heat loading and supply air flow conditions.

242 t't"cccdings cif Indoor Air '93. Vol. 5
MF;TII()1)
Figure l shows streakiines calculated by a computer simulation (1) (heater input of
1(K)W/m2, supply air flow rate IO0rn3/h, and supply air temperature 19"C). The heat
source is located at half of the ceiling height. Figure 1(a) shows the paths traveled by ten
marker particles from their respective starting points located 0.5m above the floor.
Initially, the particles primarily move upward, indicating a piston-like or displacement flow
in this zone until (hey are entrained by the heat source plume. In Fig.l(b), the particles
released at locations higher than, and in front of, the heater recirculate with the turbulent
air flow in the upper zone. Both of these observations were verified experimentally(I).
Thus it is reasonable to assume piston flow in the lower zone and uniform mixing in the
upper zone. Particles are transported from the lower zone to the upper zone via heat
source plumes only: thus in this model it was assumed that no recirculation occurs between
the zones except via heat sources.
In vertical dicpiicement ventilation, as shown in Fig. 2, a warm air zone is assumed to
form in the upper part of the room by the thermal plumes generated by heat sources, e.g.
office equipment, lamps, people, warm walls, etc. The warmer air will not descend below
a certain level because of its lower density. As each plume entrains anibient air, it will
grow, and therefore, the flow rate of the plumes (Vr, , i=1,2,3, ) is a function of their
height above the heat sources, Zpt. As there is no recirculation between the zones, except
via heat source plumes, in steady conditions the warm zone height, Z, is the point at which
the sum of all the plume flow rates is equal to the supply air flow rate, V. Therefore:
VPt+VPZ+VP3+=V
Air change effectiveness
Assuming a room is dosed with a tracer gas in the supply duct until equilibrium is
obtained and then dosing is turned off (tracer decay test), the mass balance equations for
the dirty zone I are:
(1)
Vt((iCt/dt) = VC2(()) -VCt(t); (0 < t S V2/V) (2)
Vt(dCl/dt) = -VCl(t); (V2/V < t < ') (3)
where t denotes tiine V the supply air ftow rate Ct and C2 are the contaminant
concentrations in zone 1 and 2, and, V1 and V2 are the volumes in zone I and 2. Solving
the above equations for Ct allows a determination of the room mean age of air, < t>, and
air change effectiveness, eA:
C1(t) = Ct(0) = CZ(U); (0 < t S V2/V) (4)
Ct(t) = C (0) exp(-(V/Vt)(t-VZ/V)l;
~ (V2/V < t < ') (5)
<t> _ (V
+Vt2) / (2VV) (6)
eA = tn/<Z> = 2/[1+(Vt/V)2) (7)
where V'=V t+V2, and tn=V/V. Thus, the air change effectiveness can be expressed as a
function of the dirty zone volutne ratio V t/V, where the dirty zone volume ratio is a
function only of the heat load and room ventilation conditions.

Proceedings of Indoor Air '93. Vol. 5
Contaminant removal effectiveness
243
Figure 3 diagrams a single room ventilation system including recirculation and an air
cleaner located in the supply air system. Contaminant generation can occur in the system
at the rate of No, in zone I at the rate of Nt and in zone 2 at the rate of N2. Although in
reality there will be some lateral diffusion in the lower zone, for the purposes of this
model it is adequate to assume that N2 is immediately entrained into thermal plumes.
Mass balance equations for zone I and zone 2 are:
VC2 + Nt + N2 = VCl (8)
VCin + NZ = VC2 + N2
with the concentration of contaminant in the supply air given by: (9)
Cin = (1-et))(1- a)Ct + (1-e0)QCn + (No/V) (]O)
and CO is the concentration of contaminant in outside air; N0, Nt, and N2 are the
contaminant generation rates in the supply air system, zone 1, and zone 2, respectively; eo
is the air cleaner efficiency; and a is the outside air ratio. For the simple case where
Ct)=O, NO={), eO=0 and a=l:
Ct = (NI +NZ)/V (11)
C =q (12)
e~ = Ce(-)/<C(°°)> = Ct/((CtVt+CZV2)/V) = 1/(Vi/V) (13)
with Ce(-) as the concentration of contaminant at exhaust and <C(-)> as the room mean
concentration of contaminant. The contaminant removal effectiveness can be expressed as
a function of the dirty zone volume ratio, V t/V, which is only a function of the heat load,
and room ventilation conditions. The dirty zone volume ratio can be estimated by
equations proposed by Koganei (1) which are:
H (l-VI/V) = 0.64 (bl)0.5Ar-0.2 + h (14)
with: Ar = g(3 (Ta- Tin) b/uin2 (15)
Ta-Tin = P/(2VpCp) (16)
where b is the height of the diffuser opening (m), I is the length of the diffuser opening
(in), N is the room height (in), g is the gravitational acceleration (m/s2), P is the heat load
(W), V is the supply air flow rate (m3/s), T8 is the mean room air temperature (°K), Tin is
the supply air temperature (°K), ui. is the diffuser inlet air velocity (m/s), C is the
specific heat of air (1/kg °K), P is the coefficient of volumetric expansion (/°K) , and p
is the density of air (kg/rn3).
An experiment performed in a vertical displacement ventilation test room (4.2m x 4.4m x
3.2m) provides data to check the validity of this model (4). The tests were conducted at
two different flow rates (510 and 17U(hn3/h) and two heat load conditions (13 and
44W/m2) using SF6 and tobacco smoke as contaminants.

244 t'rocccdings of Indoor Air '93. Vol. 5
RESU1,1'S'
Figure 4 presents the predicted air change effectiveness calculated from equation (7)
compared to earlier model predictions by Mundt (2) and Mathisen (3) (note that the
recirculation-frorn zone I-to- zone 2 is set to zero for references (2, 3)). As shown in the
figure, when the dirty zone does not exist (V t/V = 0), this model predicts ea=2, which
agrees with the expected piston flow condition. When the clean zone dnes not exist
(Vt/V = 1), ea of I is predicted - again in agreement with the observed fully mixed flow
conditions in the dirty zone. Thus, these results are more intuitively correct than the
predictions of references (2,3). 1
Figure 5(a) shows the contaminant removal effectiveness, ec, as calculated in eyuation(13).
Experimental results for several kinds of contaminants indicate values of ec which vary
from 1.3 to 3,6 at V t[V=Q.55 and 0.31.
Figure 5(b) shows the contaminant removal effectiveness, ec, as a function of air cleaner
efficiency eo, and outside air ratio, Q, with outside air having C,=t) and zero contaminant
generation rates in the system, Nfl=(), V t/V=0.4 (this is the occupied zone height of 1.8m
assuming a room ceiling height of 3m). As v appr'oaches 0 (no outside air), higher
efficiency air cleaning is required to achieve the equivalent contaminant removal
effectiveness values.
Figure 6 shows an example of the predicted dirty zone volume ratio calculated from
eyuations( l4), (15) and (16) as a function of flow rate and heat load. For these particular
curves, b=0.25m, 1=l.tim, h=1.Grn, 11=3:5m and the floor area was 15m2.
UISLUSSI()N
This model calculates air change effectiveness based on the room mean age of air. The
calculations can also be based on the average age of air in the occupied space or at
breathing level by using the appropriate local contaminant concentration value in this
model.
Contaminant removal effectiveness is evaluated by assuming that contaminants added to
the lower zone are immediately transported to the upper zone via heat source plumes and
thus have no effect on the contaminant concentrations in the lower zone. Experimental
results show that the lower zone does not have pure piston flow since low levels of
contaminants were measured in this zone with a clean air supply to the test room. 33te
variance in the data, shown in Fig. 5(a), may be due to different diffusion and recirculation
rates for each of the contaminants. This may be due to their different densities and the
varying temperature of the contaminant sources. A more exact simulation should include
diffusion and recirculation terms in the lower zone, however, the fundamental
characteristics of displacement ventilation phenomena are represented well in this model.
This modeling is based on the existence of thermal plumes within the room. When there
arc no heat sources, the upper warm dirty zone is not forrned, and thus the dirty zone
volume ratio becomes 0, corresponding to piston flow conditions over the entire room. As
shown in Fig. 6, the dirty zone volume ratio Vt/V becomes small when the heat load is
small. llowever, in the actual phenomena with only small or nonexistent heat loads, the

I'iocccdings of Indoor Air '93, Vol. 5
piston flow condition may be very unstable or sensitive to small disturbances, so, there
may be some diffusi:)n and not perfect piston flow.
CONCLUSIONS
6YJ
Modeling of vertical displacement ventilation has been improved by assuming that:
1) piston flow in the lower "clean" zone and uniform mixing in the upper "dirty" zone; and
2) recirculation between the zones does not occur except via heat source plumes. The
primary strengths of this model are:
1) Fundamental characteristics of displacement ventilation systems are more realistically
simulated by including consideration of heat load, room ventilation, and system conditions
(e.g. outside air ratio, air cleaner location and efficiency, total heat load, supply air flow
rate, etc).
2) It is unnecessary to know the details of the plume flow conditions. These are
complicated functions of various conditions (e.g. surface temperature and the shape of the
heat load, and temperature around the heat loads, etc.).
ACKNOWLEDGEMEN'T
We are pleased to acknowlege that this study is being partially funded by Philip Morris,
USA. We also gratefully acknowledge the support from Asahi Kogyosha Co., Ltd. for Dr.
Koganei as a Visiting Scholar at the Indoor Environment Program at Virginia Tech.
REFERENCES
l. Koganei M., Buenconsejo N. Jr., Inokuchi M., and Fujii T., "Applicability of
displacement ventilation to offices in Japan." IAQ 91: Healthy Buildings, 1991.
2. Mundt E., "Temperature gradients and convective flows with displacement ventilation.
"Dissertation. Royal Institute of Technology, Stockholm, 1991.
3. Mathisen H. M., "Analysis and evaluation of displacement ventilation." Dissertation,
University of Technology, Trondheim, Norway, 1989.
4. Olesen B. W., Koganei M., Holbrook G: T., Seelen J., Woods J. E., "Evaluation of a
vertical displacement ventilation system." Indoor Air 93, 1993.
Figure l. Streakiines of marker particles in computer flow simulation.

246
Miu inE
t
(t ~ t ~ + f + +t f f ~ ~ f f
~ ~ VAfigure 2. Schematic of two-zone model.
Ea
1
oCo
r'rtuccdings of Indoor Air '93, Voi. 5
Figure 3. Diagram of test room and FtVAC system model.
F'iston flow
Complete mixing
0 Vt/V 1
Figure 4. Predicted air change effectiveness.
06 r- ................... .................................. ..... .................
IUOWVm2
V t/V 44RrJm2 I
0.4 ~
I
13Wifn` I
0 200 400 600
V, (m'Lh)
Figure 6. Predicted values of V t/V as a function
of the supply flow rate.
(a) Comparison with measurements at
V t/V = 0.31 & 0.55, for v=1.
1 2 3
Ec
(b) Filter efficiency required for a specified
a and Ec.
Figute 5. Predicted contaminant removal
effectiveness.
