Jump to:

Philip Morris

Appendix C Modeling the Thermal and Indoor Air Quality Performance of Vertical Displacement Ventilation Systems

Date: 15 Feb 1993
Length: 7 pages
2021578832-2021578838
Jump To Images
snapshot_pm 2021578832-2021578838

Fields

Author
Holbrook, G.T.
Koganei, M.
Olesen, B.W.
Woods, J.E.
Type
SCRT, REPORT, SCIENTIFIC
ABST, ABSTRACT
BIBL, BIBLIOGRAPHY
CHAR, CHART, GRAPH, TABLE, MAPS
DRAW, DRAWING
Area
CENTRAL FILES/PRE-DB WAREHOUSE
Document File
2021578674/2021578937/Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control
Litigation
Ppla/Produced
Characteristic
EXTR, EXTRA
Site
R107
Named Organization
Asahi Kogyosha
Indoor Environment Program
Va Polytechnic Inst + State Univ
Author (Organization)
Asahi Kogyosha
Indoor Environment Program
Va Polytechnic Inst + State Univ
Named Person
Koganei, M.
Master ID
2021578685/8936
Related Documents:
Date Loaded
07 Jan 1999
UCSF Legacy ID
lkc33e00

Document Images

Text Control

Highlight Text:

OCR Text Alignment:

Image Control

Image Rotation:

Image Size:

Page 1: lkc33e00 Log in for more options!
Progre.s Report Evaluation of Ventilation Syst.ms G Feliruary 15, 1993 APPENDIX C Modeling the Thermal and Indoor Air Quality Performance of Vertical Displacement Ventilation Systems Physioal Systems Tasks 3
Page 2: lkc33e00 Log in for more options!
MODELING THE THERMAL AND INDOOR AIR QUALITY PERFORMANCE OF VERTICAL DISPLACEMENT VENTILATION SYSTEMS Makoto Koganeii, G. Thomas Holbrook2, Bjarne W. Olesen2, James E. Woods2 1Research & Development Center, Asahi Kogyosha Co., Ltd., Japan 2Indoor Environment Program, College of Architecture and Urban Studies, Virginia Polytechnic Institute and State University ABSTRACT To predict the thermal and indoor air quality performance of vertical displacement ventilation systems using two-zone modeling, it is necessary to account for the different nature of the air flow due to thermal and contaminant mixing within these zones. Two zone modeling of vertical displacement ventilation was performed assuming piston flow in the clean zone, uniform mixing in the dirty zone, and no recirculation between the zones except via heat source plumes. The resulting equations for air change effectiveness and contaminant removal effectiveness more closely match observed vertical displacement ventilation performance than previous studies, especially under non-isothermal conditions with heat sources. INTRODUCTION Previous experiments with a vertical displacement ventilation system performed in a 2.8m x 2.6m x 3m test room during early summer and winter show that a room with heat loads (30-170 W/m2) is divided into two zones: a lower, "clean" (unmixed), zone with temperature stratification connected by heat source plumes to an upper, "dirty" (mixed) zone with an almost uniform temperature distribution (1). Contaminants added to the upper zone mix with the turbulent air flow in that zone while contaminants added to the lower zone do not mix but, ascend until entrained by heat source plumes. Past attempts to mathematically model vertical displacement ventilation systems have not fully accounted for the different nature of the air flow and temperature distributions within the upper and lower zones (2, 3). These models have typically assumed uniform temperatures and contaminant mixing within each zone, and a recirculation factor applied between the two zones. For these models, air change effectiveness and contaminant removal effectiveness can only be evaluated for a specified recirculation factor and clean zone height, both of which are not easily quantified for a given room condition. The effects of internal heat loads and temperature stratification on air flow patterns and the resulting air quality have not been accounted for in these models. Results described herein, indicate that modeling a vertical displacement ventilation system is improved by assuming: 1) piston flow in the clean zone and uniform mixing in the dirty zone; 2) no recirculation between zones except via heat source plumes; 3) that the clean zone height can be expressed as a function of heat loading and supply air flow conditions. N O N N C1t q m (0 Cj W
Page 3: lkc33e00 Log in for more options!
METHOD Figure 1 shows streaklines calculated by a computer simulation (1) (heater input of 100W/m2, supply air flow rate 100m3/h, and supply air temperature 19°C). The heat source is located at half of the ceiling height. Figure 1(a) shows the paths traveled by ten marker particles from their respective starting points located 0.5m, above the floor. Initially, the particles primarily move upward, indicating a piston-like or displacement flow in this zone until they are entrained by the heat source plume.- In Fig.l(b), the particles released at locations higher than, and in front of, the heater recirculate with the turbulent air flow in the upper zone. Both of these observations were verified experimentally(1). Thus it is reasonable to assume piston flow in the lower zone and uniform mixing in the upper zone. Particles are transported from the lower zone to the upper zone via heat source plumes only; thus in this model it was assumed that no recirculation occurs between the zones except via heat sources. In vertical displacement ventilation, as shown in Fig. 2, a warm air zone is assumed to form in the upper part of the room by the thermal plumes generated by heat sources, e.g. office equipment, lamps, people, warm walls, etc. The warmer air will not descend below a certain level because of its lower density. As each plume entrains ambient air, it will grow, and therefore, the flow rate of the plumes (Vpj , i=1,2,3, -) is a function of their height above the heat sources, Zpj. As there is no recirculation between the zones, except via heat source plumes, in steady conditions the warm zone height, Z, is the point at which the sum of all the plume flow rates is equal to the supply air flow rate, V. Therefore: VP1+VpZ+VP3+-=V Air change effectiveness Assuming a room is dosed with a tracer gas in the supply duct until equilibrium is obtained and then dosing is turned off (tracer decay test), the mass balance equations for the dirty zone 1 are: V1(dCl/dt) = VC2(0) -VCl(t); (0 <.t 5 V2/V) V1(dCl/dt) = -VC1(c); (V2/V < t < -) (1) where t denotes time V the supply air flow rate C1 and C2 are the contaminant concentrations in zone 1 and 2, and, Vl and V2 are the volumes in zone 1 and 2. Solving the above equations for Cl allows a determination of the room mean age of air, < t>, and air change effectiveness, ea: C1(t) = C1(0) = C2(0); (0 < t S VZ/V) (4) N ~ C1(t) = C (0) 2 P{-(V/V1)(t-V2/V)l; (VZ/V < t<-) (5) } <ti>=(V +Vt 2) / (2VV2 t a = ~n/<T> = 2/[ 1+(V 1/V) ] (7) !v ~ where V=V1+V2, and tII V/V. Thus, the air change effectiveness can be expressed as a function of the dirty zone volume ratio V 1/V, where the dirty zone volume ratio is a function only of the heat load and room ventilation conditions.
Page 4: lkc33e00 Log in for more options!
Contaminant removal effectiveness Figure 3 diagrams a single room ventilation system including recirculation and an air cleaner located in the supply air system. Contaminant generation can occur in the system at the rate of Na, in zone 1 at the rate of Nl and in zone 2 at the rate of N2. Although in reality there will be some lateral diffusion in the lower zone, for the purposes of this model it is adequate to assume that N2 is immediately entrained into thermal plumes. Mass balance equations for zone 1 and zone 2 are: VC2 + N1 + N2 = VC1 (8) VC;n + N2 = VC2 + N2 . (9) with the concentration of contaminant in the supply air given by: C;a = (1-eo)(1- a)Cl + (1-e0)oq + (NO/V) (10) and CO is the concentration of contaminant in outside air; NQ, N1, and N2 are the contaminant generation rates in the supply air system, zone 1, and zone 2, respectively; eo is the air cleaner efficiency; and a is the outside air ratio. For the simple case where C0=0, Np=O, eo=O and o=1: C1= (N1+NZ)/V (11) C,, 0 (12) e~ = Ce(»)/<C(-)> = C1/((CtVt+C.2V2)/V) = 1/(V1/V) (13) with C,(») as the concentration of contaminant at exhaust and <C(»)> as the room mean concentration of contaminant. The contaminant removal effectiveness can be expressed as a function of the dirty zone volume ratio, V1/V, which is only a function of the heat load, and room ventilation conditions. The dirty zone volume ratio can be estimated by equations proposed by Koganei (1) which are: H (1-V 1/V) = 0.64 (bl)osAr-u + h (14) with: Ar = go (Ta Tin) b/uin2 (15) Ta T;n = P/(2VpCp) (16) where b is the height of the diffuser opening (m), 1 is the length of the diffuser opening (m), H is the room height (m), g is the gravitational acceleration (m/s2), P is the heat load (W), V is the supply air flow rate (m3/s). Ta is the mean room air temperature (°K), T;. is the supply air temperature (°K), ui, is the diffuser inlet air velocity (m/s),C., is the specific heat of air (J/kg °K), 0 is the coefficient of volumetric expansion (I/°K) , and p is the density of air (kg/m3). An experiment performed in a vertical displacement ventilation test room (4.2m x 4.4m x 3.2m) provides data to check the validity of this model (4). The tests were conducted at two different flow rates (510 and 1700m3/h) and two heat load conditions (13 and 44W/m2) using SF6 and tobacco smoke as contaminants.
Page 5: lkc33e00 Log in for more options!
RESULTS Figure 4 presents the predicted air change effectiveness calculated from equation (7) compared to earlier model predictions by Mundt (2) and Mathisen (3) (note that the recirculation from zone 1-to- zone 2 is set to zero for references (2, 3)). As shown in the figure, when the dirty zone does not exist (Vi/V = 0), this model predicts ea 2, which agrees with the expected piston flow condition. When the clean zone does not exist (Vl/V = 1), ca of 1 is predicted - again in agreement with the observed fully mixed flow conditions in the dirty zone. Thus, these results are more intuitively correct than the predictions of references (2,3). Figure 5(a) shows the contaminant removal effectiveness, ec, as calculated in equation(13). Experimental results for several kinds of contaminants indicate values of ec which vary from 1.3 to 3.6 at V 1/V=0.55 and 0.31. Figure 5(b) shows the contaminant removal effectiveness, cc, as a function of air cleaner efficiency eo, and outside air ratio, a, with outside air having C9=0 and zero contaminant generation rates in the system, No=O, V l/V=0.4 (this is the occupied zone height of 1.8m assuming a room ceiling height of,3m). As a approaches 0 (no outside air), higher efficiency air cleaning is required to achieve the equivalent contaminant removal effectiveness values. Figure 6 shows an example of the predicted dirty zone volume ratio calculated from equations(14), (15) and (16) as a function of flow rate and heat load. For these particular curves, b=0.25m,1=1.6m, h=1.6m, H=3.5m, and the floor area was 15m2. DISCUSSION This model calculates air change effectiveness based on the room mean age of air. The calculations can also be based on the average age of air in the occupied space or at breathing level by using the appropriate local contaminant concentration value in this model. Contaminant removal effectiveness is evaluated by assuming that contaminants added to the lower zone are immediately transported to the upper zone via heat source plumes and thus have no effect on the contaminant concentrations in the lower zone. Experimental results show that the lower zone does not have pure piston flow since low levels of contaminants were measured in this zone with a clean air supply to the test room. The variance in the data, shown in Fig. 5(a), may be due to different diffusion and recirculation rates for each of the contaminants. This may be due to their different densities and the varying temperature of the contaminant sources. A more exact simulation should include diffusion and recirculation terms in the lower zone, however, the fundamental characteristics of displacement ventilation phenomena are represented well in this model. This modeling is based on the existence of thermal plumes within the room. When there are no heat sources, the upper warm dirty zone is not formed, and thus the dirty zone volume ratio becomes 0, corresponding to piston flow conditions over the entire room. As shown in Fig. 6, the dirty zone volume ratio Vl/V becomes small when the heat load is small. However, in the actual phenomena with only small or nonexistent heat loads, the
Page 6: lkc33e00 Log in for more options!
piston flow condition may be very unstable or sensitive to small disturbances, so, there may be some diffusion and not perfect piston flow. CONCLUSIONS Modeling of vertical displacement ventilation has been improved by assuming that: 1) piston flow in the lower "clean" zone and uniform mixing in the upper "dirty" zone; and 2) recirculation between the zones does not occur except via heat source plumes. The primary strengths of this model are: 1) Fundamental characteristics of displacement ventilation systems are more realistically simulated by including consideration of heat load, room ventilation, and system conditions (e.g. outside air ratio, air cleaner location and efficiency, total heat load, supply air flow rate, etc). 2) It is unnecessary to know the details of the plume flow conditions. These are complicated functions of various conditions (e.g. surface temperature and the shape of the heat load, and temperature around the heat loads, etc.). ACKNOWLEDGEMENT We are pleased to acknowlege that this study is being partially funded by Philip Morris, USA. We also gratefully acknowledge the support from Asahi Kogyosha Co., Ltd for Dr. Koganei as a Visiting Scholar at the Indoor Environment Program at Virginia Tech. REFERENCES 1. Koganei M., Buenconsejo N. Jr., Inokuchi M., and Fujii T., "Applicability of displacement ventilation to offices in Japan." IAQ 91: Healthy Buildings, 1991. 2. Mundt E., "Temperature gradients and convective flows with displacement ventilation. "Dissertation, Royal Institute of Technology, Stockholm, 1991. 3. Mathisen H. M., "Analysis and evaluation of displacement ventilation." Dissertation, University of Technology, Trondheim, Norway, 1989. 4. Olesen B. W., Koganei' M., Holbrook G. T., Seelen J., Woods J. E., "Evaluation of a vertical displacement ventilation system." Indoor Air 93, 1993. Figure 1. Streakiines of marker particles in computer flow simulation.
Page 7: lkc33e00 Log in for more options!
~ c n C C C" ~ CO ~ LJ_zp1 Pistoa ,r / flow 1 itttttttttttTTt T Figure 2 Schematic of two-zone model. 0.6 Vi/V 0.4 0.2 C1 ZOM I 1 C1 Ea No S'~L ~ _'~sr cod ~ Zone 2 Pi' C2 v Figure 3. Diagram of test room and HVAC system model. Pfsoon flow Complete mixing 0 VI/V 1 Figure 4. Predicted air change effectiveness compared with measurements. 10ow/m2 ; I Z 44W/m ~ ~ s . 0 200 400 600 V, (m3l.1) , Figure 6. Predicted values of V 1/V as a function of the supply flow rate. (a) Comparison with measurements at V 1/V = 0.31 & 0.55, for a=1. N N r CA 1 2 3 Ec m (b) Filter efficiency required for a specifi Q and le. Figure 5. Predicted contaminant removal effectiveness.

Text Control

Highlight Text:

OCR Text Alignment:

Image Control

Image Rotation:

Image Size: