Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control Status Report: Design Process of the Research and Demonstration Facility Phase II
Fields
- Type
- REPT, REPORT, OTHER
- BIBL, BIBLIOGRAPHY
- BUDG, BUDGET, BUDGET REVIEW
- CHAR, CHART, GRAPH, TABLE, MAPS
- BIBL, BIBLIOGRAPHY
- Area
- CENTRAL FILES/PRE-DB WAREHOUSE
- Site
- R107
- Named Person
- Arora, S.
- Baker, K.W.
- Davis, A.J.
- Decker, V.F.
- Galloway, W.
- Hanna, D.B.
- Harmon, J.J.
- Kuykendall, J.G.
- Olesen, B.
- Schubert, R.P.
- Seelen, J.
- Steger, C.W.
- Warren, S.P.
- Woods, J.
- Baker, K.W.
- Named Organization
- Ashrae, American Society of Heating, Refrigerating + Air-Conditioning Engineers
- Avis Construction
- Breakell
- Building Specialists
- Center for Innovative Technology
- Commonwealth of Va
- Debusk Shelor
- Hc Yu + Associates
- Iep Research Team
- Indoor Environment Program
- Johnson Controls
- Landis Gyr
- Lionberger Construction
- Lithonia
- Mero
- Natl Concrete Masonry Assn
- Roanoke Times + World News
- Rollins + Associates
- Sh Sewell
- Simplex
- Univ Facilit Planning Construction Group
- Va Dept of Energy + Buildings
- Va Dept of Engineering + Buildings
- Va Division of Engineering + Buildings
- Va Tech
- Wg Simmons
- Ar Neety
- Avis Construction
- Recipient (Organization)
- PM, Philip Morris
- Document File
- 2021578674/2021578937/Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control
- Litigation
- Ppla/Produced
- Author (Organization)
- Va Tech
- Master ID
- 2021578685/8936
Related Documents:- 2021578685-8936 Period 2 Project Report Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control 920516 to 930831
- 2021578705-8708 Comparative Evaluation of Displacement Ventilation and Conventional Vav Systems for Indoor Air Quality Control
- 2021578709
- 2021578711-8717 Proposal to Philip Morris, Usa for Continuation of Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control
- 2021578755-8762 Indoor Environment Program Meeting with the Science Advisory Committee 930129 Minutes and Action Items
- 2021578764-8780 Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control Progress Report 920515 - 921115
- 2021578781-8785 Appendix A Abstracts for Indoor Air '93
- 2021578786-8790 Appendix B Project Overview Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control
- 2021578791-8798 Appendix C Performance Criteria
- 2021578800-8815 Evaluation of Displacement Ventilation and Conventional Variable Air Volume Systems for Indoor Air Quality Control Progress Report 921116 - 930215
- 2021578816-8824 Appendix A Minutes of the 930129 Science Advisory Committee Meeting
- 2021578825-8831 Appendix B Rational Building Performance and Prescriptive Criteria for Improved Indoor Environmental Quality
- 2021578832-8838 Appendix C Modeling the Thermal and Indoor Air Quality Performance of Vertical Displacement Ventilation Systems
- 2021578839-8845 Appendix D Evaluation of A Vertical Displacement Ventilation System
- 2021578847-8855 Design and Construction of A Facility for Research and Demonstration of Healthy Building Concepts
- 2021578856 Indoor Air '93 Proceedings of the 6th International Conference on Indoor Air Quality and Climate Volume 3. Combustion Products, Risk Assessment, Policies
- 2021578857-8862 Rational Building Performance and Prescriptive Criteria for Improved Indoor Environmental Quality
- 2021578863 Modeling the Thermal and Indoor Air Quality Performance of Vertical Displacement Ventilation Systems
- 2021578864 Indoor Air '93 Proceedings of the 6th International Conference on Indoor Air Quality and Climate Volume 5. Ventilation
- 2021578865-8870 Modeling the Thermal and Indoor Air Quality Performance of Vertical Displacement Ventilation Systems
- 2021578871 Evaluation of A Vertical Displacement Ventilation System
- 2021578872 Indoor Air '93 Proceedings of the 6th International Conference on Indoor Air Quality and Climate Volume 5. Ventilation
- 2021578873-8878 Evaluation of A Vertical Displacement Ventilation System
- 2021578879 A Characterization of Methodologies for Assessing Human Responses to the Indoor Environment
- 2021578880 Indoor Air '93 Proceedings of the 6th International Conference on Indoor Air Quality and Climate Volume 1. Health Effects
- 2021578881-8886 A Characterization of Methodologies for Assessing Human Responses to the Indoor Environment
- 2021578887-8897 A Case Study: Cost Implications for Hvac Commissioning
- 2021578898-8903 Appendix A Specification Section 15995: Commissioning of Hvac System Contract Specifications for Architecture Research and Demonstration Facility Phase II, Virginia Polytechnic Institute and State University, College of Architecture and Urban Studies, Blacksburg Virginia, Rev. 11 930800
- 2021578905 Fluid Filtration: Gas Volume I A Symposium Sponsored by Astm Committee F-21 on Filtration and the American Program Committee of the Filtration Society Philadelphia, Pa, 861020 - 861022
- 2021578906-8926 Filtration As A Method for Air Quality Control in Occupied Spaces
- 2021578927 Indoor Air Volume 5 Buildings, Ventilation and Thermal Climate
- 2021578928-8932
- 2021578934-8936 Economic Modeling of Vav and Vdv Systems in Rdf II
- Characteristic
- EXTR, EXTRA
- Date Loaded
- 07 Jan 1999
- UCSF Legacy ID
- ckc33e00
Document Images
Statua R"M Er.luation of Ventilation Syst.ms
November 18,1992
serving the other office. The third air handling unit serves the conference room, the corridor and
the instrumentation room.
12.1 THE CONVENTIONAL VARIABLE AIR VOLUME VENTILATION SYSTEM
The HVAC system that serves one office space is a conventional variabie air volume (VAV)
system. A conventional VAV system is a system which might be designed to serve a typical
small to medium size building. Design criteria for indoor conditions are 76 F (dry bulb) in the
summer, and 72 F (dry bulb) in the winter. The air handling unit (AHU) has a filter (35%
efficiency), hot water preheat coil, and chilled water cooling coil. The volume being delivered to
the system will be determined by the VAV box (with reheat) serving the space. Air will be
introduced into the room through perforated ceiling diffusers. Air will be returned through the
light
fixtures and the ceiling plenum. To ensure that the office Is negative with regard to the
conference room and the corridor, an exhaust fan (300 cfm) is added. Lining inside ducts is
allowed and applied were necessary.
Although the protocol did not allow the research team to influence the design of the conventional
system, some concerns the team had were discussed with the engineer. The supply air diffusers
are located adjacent to the light fixtures that will return the air from the room. This might have
a negative impact on the air distribution. The design is not changed but the supply air ducts will
be constructed of flexible duct to allow simple modification. The control sequence for the system
allows the VAV box to go to "zero pinch down", meaning under certain conditions that no outdoor
air is supplied to the room for energy efficiency purposes. This is not in compliance with
ASHRAE 62-1989, calling for 20 cfm outside air per person. The system control sequence is
modified so that a minimum of 200 cfm outside air (10 persons) is provided for all operating
modes. For research purposes provisions are made to allow future installation of a high efficiency
filter (85%) in addition to the 35% efficiency filter. Because of concerns for microbiological
contamination of the ducts, lining is not allowed 3 feet from cooling coil, humidifier or other
wetted
surfaces.
Design of a Research and Demonstration Facil'tty 7

Status Report Evaluation of Ventif.tbn Systems
November 18,1992
12.2 THE VERTICAL DISPLACEMENT VENTILATION SYSTEM
The vertical displacement ventilation system Is similar to the FACT (Filtered Air Control
Technology) system.- Design criteria for Indoor conditions are 76 F (dry bulb) in the summer, and
72 F (dry bulb) in the winter. The supply temperature has to be such that the system will answer
the cooling load required, yet not cause any draft effects. The air handling unit (AHU) has two
filters (35% and 85%), hot water preheat coil, chilled water cooling coil, and a terminal box
(without reheat). The air from this unit will mix with return air in a fan powered box with reheat
to provide a fixed air flow into the space. The supply air is filtered by a carbon filter and an
electrostatic filter and introduced into the room through a perforated floor and carpet. Air will be
returned through ceiling diffusers acting as return air grilles, and through ducts back to the unit.
A high efficiency filter is installed in the recirculated airstream. To ensure that the office is
negative with regard to the conference room and the corridor, an exhaust fan (300 cfm) is added.
For research purposes provisions will be made so that all filters can be bypassed. The control
sequence is modified so that a minimum of 200 cfm outside air (10 persons) is provided for all
operating modes (for the same reasons as for the conventional system).
1.2.3 THE SYSTEM SERVING THE CONFERENCE ROOM, INSTRUMENTATION ROOM, AND
CORRIDOR
The third air handling unit serves the conference room, the instrumentation room and the corridor.
The conference room will also serve as adaptation room for panels judging the air quality in the
offices and therefore the air needs to be as clean, i.e. odor free, as possible. The equipment in
the instrumentation room requires both thermal and humidity control. In order to prevent cross
contamination between the offices, the offices will have negative pressure with regard to the
conference room and corridor. Design criteria for indoor conditions are 76 F (dry bulb), 509'0
Relative Humidity in the summer, and 72 F (dry bulb), 30 % Relative Humidity in the winter. To
comply with these requirements, the third air handling unit is a constant volume HVAC system
with 100% outside. The unit has a pre-filter and final filter (respectively 30%o and 85%
efficiency),
N
0
N
N
~
~
O
Design of a Research and Demonstration Faotliry 8

staa. R.port Evalwtion of V.ntil.tion Syst.ms
November 18,1992
a carbon filter with final filter (85% efficiency), hot water preheat coil, chilled water cooling
coil,
a humidifier, and a supply fan. Constant volume boxes with heating coils will ensure proper air
flow to each space. Air will be supplied through ceiiing diffusers in the conference room and
instrumentation room, and through jets in the corridor. Air will be relieved through the mechanical
equipment room to the outside. A vestibule and extra weather stripping was added to the doors
in the corridor to minimize air infiltration.
1.2.4 OTHER MECHANICAL SYSTEMS
Chilled water is provided by a nominal 15 ton air cooled water chiller serving all three air
handling
units. Heating water is provided by a gas fired cast iron hot water boiler serving the three air
handling units and the two unit heaters.
The mechanical room does not need comfortable conditions but only freeze protection for the
equipment. Two unit heaters (hot water), placed on either side of the room, will serve this room.
The bathrooms have both a separate exhaust fan. Initially the fans were connected to the light
switch. To ensure that these room are always negative with regard to the rest of the building the
design was modified so that the exhaust fans will run 24 hours a day.
The two bathrooms in the facility have an in-line water heater. There is a mob-sink in the
mechanical room, and a'rough-in" for one sink in the instrumentation room. A water cooler is
located in the corridor.
1.2.5 COMMISSIONING
~
The purpose of the commissioning process, as defined in the Commonwealth of Virginia Capital
Outlay Manual is: ~U
o to document cteariy the design intent
Design of a Research and Demonstraoon Facility

St.wa R.port Evaluation of Ventilation Systeros
November 18,1992
o to verify that the system instaiiation and performance is in accordance with the plans and
specifications and design intent
o to train the owner's operators so that they fully understand the design intent and the
operation and maintenance requirements of the equipment provided to accomplish that
end, and to provide them with all necessary technical information required for a complete
understanding of the system
The commissioning process helps to provide assurance of healthy indoor environments by
verification of the system performance criteria. Moreover it helps to realize economic benefits
through reduced change orders, quicker solutions to problems arising during design and
construction, and to lower operating and maintenance costs. The task requires a complete
understanding of the performance criteria and design intent as well as of the building systems as
instaiied. While the designers of the building and/or systems are suitable candidates to perform
the task, another school of thought recommends that an independent person/group be appointed
as the commissioning authority to allow for an independent evaluation of the service systems as
designed and installed. As the mechanical system is a critical component of this test facility, the
designers of the system have been retained as the commissioning authority. In an attempt to
identify the monetary value assigned by the contractors to the commissioning process, the bidders
were asked to provide this as an add alternate item (Chapter 2, Table 2). The cost effectiveness
of this commissioning process including the cost for the commissioning authority and the
mechanical contractors are now being analyzed.
J
Design of a Research and Demonsiraoon Facility 10

Status Report Evaluation of Ventilation systems
November 18,1992
2 THE PROJECT BUDGET
Based on a rough draft of the drawings an estimate of construction cost was prepared by
Facilities Planning and Construction (FPC) In September 1991 (See Table 4). A project budget
was made and granted by the sponsor. After completion of the design, an outside estimator was
asked to give a cost estimate on the construction. The first estimate was much higher than was
expected and design changes needed to be made to bring the project in budget Since IAQ was
a research issue and the HVAC system was part of that research, no cost savings were possible
in this division. Because of the phased construction of this project, Phase II was to be compatible
with Phase I. Therefore major architectural components, i.e. space frame and the masonry walls
could not be changed. Compromises were made in the architectural design and the engineering
design to get the project within budget, without compromising the IAQ or the architectural intent.
Instead the strategy to reduce cost focused on those items that were non-mandatory or
redundant. Additional cost savings were realized through changes in materials used for the
interior walls and the roof. It was anticipated that a good preventive maintenance program would
compensate for the loss of durability inherent to these new materials. This chapter describes the
several cost savings that were made in chronological order. Involved in the process of reviewing
the cost estimate and bringing the project within budget are:
Jack Davis and Bill Galloway, Bob Schubert, architects
Dixon Hanna, College of Architecture
Jim Woods, Bjame Olesen, Julie Seelen, Sanjay Arora, IEP-research team
John Kuykendall, Ken Baker, Steve Warren, Virgil Decker, Facilities Planning and Construction
Rollins & Associates, P.C., estimators
2.1 COST ESTIMATE
27 March 1992 The first cost estimate comes in at $796,255. Table 1 gives the summary of the
cost estimates by Rollins and Associates. The three biggest cost items are exterior walls, HVAC
rne Project audget 11

Status Rspcrt Evdwdon of Ventilation 9yst.ms
Nbvmbec 18.1992
systems, and the building controls. The HVAC systems cost are higher than initially anticipated
for two reasons: First, the project is decoupled form the EPRI-project and therefore it is
necessary to provide for a separate chiller package and a third airhandling unit to serve the other
occupied spaces. Second, during the design of the systems, and development of the protocol,
the research became better understood and several changes and extra items were added to the
systems (more efficient filters) during design. The cost for the building controls is based upon
more measuring points than necessary. Moreover, this system will be donated (both material and
labor) and the cost of this item should not be included in the construction cost.
Items proposed to change:
1) The exterior walls have a bituminous damp proofing between the veneer and the backup
masonry which has a big cost to it. Since this damp proofing is not necessary, this item
is deleted. To bring the cost further down, the bi-axial block is changed to (cheaper)
standard CMU.
2) The estimators included a markup that assumed a prime overhead on material, labor, and
equipment of 12%0, bond of 1%, and escalation of 310/0. Because of the competitive market
the prime overhead can be reduced to 10%, and bond to 0.75a. Since the project is to
be built this summer, no escalation needs to be encumbered. The markup can be
reduced which brings the base bid down considerably.
3) Some items on the drawings and in the specifications needed clarification (the side walk
edge restraint and the raised floor) and were less in cost than assumed by the estimators.
4) Items provided by the University (landscaping, site lighting, signage, and
inspection and testing) should not be included in the estimate.
5) Add a general contingency of 5%.
6) Reiterate the cost of space frame assembly and roofing (compared to Phase I they seem
to be high).
7) Excess paver block that needs to be removed can be reused.
8) The roof paver ballast is available and can be an owner furnished item.
The Project Budget 12

siaws Report Evaluatbn of Ventilation Systsma
November 18,1992
The estimate is compared to the estimate prepared by Facilities Planning and Construction (FPC)
(See Table 4). The estimate by FPC was done September 1991, based on a rough draft of the
drawings. it was assumed that the space frame would cost $22,000, and a donation of $60,000
was encumbered. The cost of the space frame is not encumbered in the estimate by Rollins, and
will add $45,000 to the construction estimate. FPC did not include cost for possible rock
excavation, sitework, extra cost for (perforated) raised floor, the chiller package and third air
handling unit.
22 Aprii 1992 The revised estimate comes in at $723,881 (Table 1). This is the construction
estimate excluding the space frame and other costs, like A/E fees, administration, etc. (Appendix
C), which bring the total project cost to $976,000. The available funds are the $634,907 (grant)
and the donation of the building controls (assumed equal to the estimate, $105,000). To solve
the $236,000 deficit a meeting is held to review the projectlcost estimate and discuss cost
savings, starting with the costs other than building construction (categories as listed In final
project
budget, Table 3).
1) Consultant fees are very high, specially H.C.Yu. This can be explained because the
design is complicated, including three mechanical systems. The fees include supervision,
commissioning, shop-drawing review.
2) The University requires a contingency of 2 %, but FPC will use 5%.
3) Site lighting. There are several lights on the test ceii building and there will be several
lights on the building. This might be sufficient to light the building and direct surroundings.
Assuming that a parking lot will be built opposite the building site by the University, the
site lighting can be lowered to $2000.
4) The geotech testing is necessary since it is very likely that we will hit rock.
5) A/E supplemental fees are only zero if we do not have to go back to the consultants.
Since H.C.Yu has a little research going on within this project, lower this amount with
$2500. -
6) Signage includes the signs for the bathroom, lab numbers. Since there will not be many
signs required in this building, this can be lowered to $1-000.
The Project Budget 13

Table 1.
Cost estimates by Rollins and Ass. Cost items that were changed are redlined. The estimate of 27
March includes a
higher mark up, and the rock contingency is included in the foundation cost.
ff I/trah 1 tt AON 0 w 7! YN 3 Jur
oa.
fOYflAsY01t t0Af0
14R11
1~
13.St0 ti;'
?
'
'
?
~
~
$LDonR~ ,t;.Rk~35
,Y,
7xt:.
::
)
}a^.~,a}3:.
9
403 4746 4.015
StuCLn.1
407
${SQOl11d . ";
4.r, .. ..: . . . : ~: '. v:
312 . .
. 4q 7N 297 40'7
Stdn
0
4,q O.ON f.ON O.M{ OAN
~ s~v. .
90
4N
~4,p1 .;.; . . . .. ....
'
~$ 70.004
$~O~ trlN . :: }}" 4
42,916
_ N
3i :n
»}x{,x~, .;~,
`
R n0 ::n
:
.
rffOf am"
E
, .....
. . /0.0N .
R r7sN u, s a4 l ta ";:ki<~S ~
n1.ea wr.
n.so. r+w.. ,7./37
21.240 :1
DppM
+
~~~ 31.N! ZO.N7 29.9" tl.N7 !0.
. . ..,;~
y:.;,
nc
a
3,4/0
2.416
SpbytNs
Rodt CaopMmY
:
,
:.:.::.. ... . :,......; :.} , .
. . .
+
e ..
. >~ . .::.
. . . ..
lDw
wrw.r mn
7 :.. . : n . . v. :. .. ' . ...n. .
11.OM
11,ON it
,N1
11N7
11M)
PYrnEYtO
1.//S
ReNd.Mogo
1S1A11 :,.
'
'.
=
~~.~~~
: T..
.
:r
k:fi
x
HVAC
h10 x
,
kY
::;: ,~,
::
.
a
Poww tl.OM N,OtO 40.416 N.O10 AOA1~
~V
U ?lAt7
'a.:.
B~Mb CiEI1~Ot/ 4vr}`.:in:r ',':2k
0,
n}:..}:.}
v
4~:~?:::;k:
:
..
w. tlA10
elephone ,
,
}:
;/17. ;ON 2. . 2.0" t
Olloer
R.Y
~:..,. ..............,..:::::::::.. .].. ....::::.}
:.... , .
-
:xS.i ... .
. -},.
:::::. t0a zoa
t,1q ton t0a
w,e.r a.nawon
12
P9 2,N !iN 21N t,1N
_
k tlk toWiirq wrl
..,.. . ,..,
................
:
::: :.:::::::.:. . . . . . ...
.....
: 5.700 S700
:......
:.: :
: : ....
.
.
... '{:S' ' :v~
$pear Me"
-~
S.N1 3tN O.tN S.tN S.1N
TO~N670A
1 1 1. 1.
~~ 1/1 : .
.
aM1101/MOPIf>~{ ;-]}::i;'F;: }kY.k:
. r
N
/70
1 Z,730 Q,7J0 !. LT10
84nn QinpO .
M~ T"1 M.N N1.7M rM
AL Mfi MD
9Cz84STzUz

Status Report Evalwtion of Wntilation 9ystans
November 18,1992
7) The University will pick up the landscaping and the transformer (2 x $5000).
Taken into account all these changes the other cost totals to $48,700, and the budget for
construction becomes: $489,077. The construction cost, estimated by Rollins, inciuding $47,000
for the space frame and $18,828 for rock excavation, excluding the building controls, is: $646,471.
The difference between budget and estimate is: $157,394. We cannot compromise on the
research, and the space frame is essential to the college, because Phase il shouidbe compatible
with the Phase I. Moreover, $24.000 on design/construction cost is already spent. Maybe
assembly cost can be lowered by having students or technicians construct it. FPC objects
because this will take away all the warranties, If something happens, the contractor will blame it
on the space frame assembly. Other possible cost savings suggested are:
,
1) Masonry: The estimate of Rollins on masonry looks high at $22.56 per sqft. University
uses about $15.00 per sqft. Anticipated savings: $26,000.
Sitework: The sidewalks are made of CMU block. It will be cheaper to make these of
concrete. Assuming a cost of $3.00 per sqft. Anticipated savings: $10,000. Rollins
assumed that 12 feet of pavers, now covering the bay area, had to be removed, to allow
the contractor to build the foundation and wall of Phase II. Assuming less needs to be
removed: anticipated savings: $10,000.
3) Fire alarm system: A fire alarm system Is not required by code, since all occupied rooms
have a direct access to the outside. The University will recommend but not mandate a
fire alarm system. Anticipated cost savings: $11,090. This also saves $100 on other cost,
since the connection to the University fire alarm system is not necessary.
Metals (including space frame and roofing): Mero (space frame manufacturer) will be
asked their estimate on cost of the erection of the frame. Assuming that 3 technicians
assemble the frame in two weeks, plus the cost of a crane to lift the frame in one day,
total erection should cost about $12,000. Anticipated savings: $5000. Rollins estimated
the cost of putting the paver ballast on the roof at $1.05 per sqft. This seems very high.
Anticipated savings: $2000.
The Project Budget 15

gtat," R"Wrt Ewlu.tlon of Ventpation 8ay.tsms
November 18,1992
5) Equipment catwalks and mezzanine: Since there is a roof access in the Phase I building,
there is no need for it in the Phase II. The cost for a scuttle can be deleted ($424), as
well as the ladder to the catwalk, the ladder to the roof and the railings on the catwalk
($2604). Total savings: $3030. No roof access means that the catwalk does not have to
be a supported floor. Originally it was anticipated that the mezzanine would be a storage
area, but the access was deleted to avoid problems with the ADA code. it is decided that
this floor does not have to be a supported floor. Both concrete floors will be changed to
gypsum board ceiling with acoustical insuiation. Assuming that the gypsum
board/insulation will cost $1200. Anticipated savings are $2300.
Specialties: Fire extinguishers will be bought by the university and are a separate item
under the total cost ($317). Pipe bollards or mop&broom/utility shelf are not necessary
($436). Custodial services needs a mop-sink and a closet ($750). Total savings on
specialties $0.
7) Doors and Windows: Change the 9 steel doors Inside to wood doors (solid, paint grade).
Anticipated savings $1000.
8) Raised floor: Because of research purposes, the floor covering In the conference cannot
be fleecy, and should be low-emitting. Reduce the 210 sqy carpet to 155 sqy. Saving:
$1240. The raiiing (ramp in corridor) should be a wall railing. Anticipated savings $800.
HVAC/Plumbing: For the initiai research we do not need all these filters. The technicians
can make the housing for some of the filters, buy the electrostatic filter, and put these In
later. Take out $5000 of the construction cost and bring this over to the other cost list,
(extra item filters). (This brings the total construction budget from $489.077 to $484.077.)
Take out of the speclcost estimate: one FILT2 (leave In two); both FILT3; one FILT4
(leave in one). Savings: $15170. In the estimate one pump to many accounted for.
Savings: $1277. Pipe identification could be $0.37 instead of $3.70 per unit for labor.
Anticipated savings: $2500. We can use the humidifier from ESL. Savings: $3282.
Anticipate that Carrier will donate the chiller package, the terminal boxes, the air handling
units, and the fans. Leave labor In the estimate. Anticipated saving because of donation:
$28,903.
The Project Budget 16