Lorillard
Ventilation for Acceptable Indoor Air Quality
Fields
- Alias
- 03735197/03735208
- Type
- SCRT, SCIENTIFIC REPORT
- BIBL, BIBLIOGRAPHY
- CHAR, CHART/GRAPH
- OUTL, OUTLINE
- BIBL, BIBLIOGRAPHY
- Area
- LEGAL DEPT FILE ROOM
- Site
- N14
- Request
- R1-004
- R1-037
- R1-132
- R1-037
- Named Organization
- Epa, Environmental Protection Agency
- Natl Aerometric Data Bank
- Niosh, Natl Inst for Occupational Safety & Health
- OSHA, Occupational Safety & Health Administration
- Standards Comm
- Natl Aerometric Data Bank
- Date Loaded
- 05 Jun 1998
- Document File
- 03735105/03735472/S and H Re Indoor Ventilation Requirements Ashrae Boca.
- Master ID
- 03735037/5472
Related Documents:- 03735038 American Red Cross Proposed Anti-Smoking Resolution
- 03735039 American Red Cross Proposed Anti-Smoking Resolution
- 03735040
- 03735041 Statement to Be Made to the Richmond Chapter of the American Red Cross (Provided by the Tobacco Institute) (Delivered by Dr. Paul Eichorn)
- 03735045-5056 Resolution I (820000) Smoking
- 03735076 American Red Cross Anti-Smoking Resolution
- 03735077 Dup of Id 03735041
- 03735078 Resolutions Presented to the American Red Cross National Convention St. Louis, Missouri, 820526 Resolution I Smoking
- 03735079-5081 American Red Cross
- 03735082-5084
- 03735085 American Red Cross
- 03735086-5087
- 03735088 American Red Cross
- 03735089 American Red Cross Anti-Smoking Resolution
- 03735090
- 03735091-5092
- 03735093 Red Cross Resolution - No Smoking Meetings/Areas
- 03735094-5095 American Red Cross Resolution Regarding Smoking in Red Cross Facilities and Associated Conferences
- 03735096 Dup of Id 03735078
- 03735097 Dup of Id 03735077
- 03735098 Smoking Policy
- 03735099-5101
- 03735102 the Attached Material - American Red Cross
- 03735103 Dup of Id 03735078
- 03735104 Board of Directors Meeting
- 03735105
- 03735106-5112 Hazards of Cigarette Smoke to Nonsmokers
- 03735113-5118 Sidestream Smoke - Fact and Fiction
- 03735119-5126 Evidence for Health Effects of Sidestream Tobacco Smoke
- 03735130
- 03735131-5132 Spc 62-1981r Roster Ventilation for Acceptable Indoor Air Quality
- 03735134-5135
- 03735136-5137 Dup of Id 03735131-5132
- 03735138-5139
- 03735141-5142 Model Variable Ventilation Requirements
- 03735143-5160 Briefing Paper Northwest Power Planning Council
- 03735161-5169 Appendix A 'pacific Northwest Electric Power Planning and Conservation Act' (Excerpt)
- 03735170-5180 Appendix B 'model Standards for New Structures,' Appendix J, Regional Conservation + Electric Power Plan, Section 305, Table 3-1. Ventilation (Draft, 830000).
- 03735181-5188 Appendix C Testimony of Walker Merryman, TI, Vice-President, Northwest Power Planning Council Hearings, Boise, Id, 830311
- 03735189 Boca Medical Building Code Hearings in Cherry Hill, Nj.
- 03735190-5191
- 03735192 Ashrae
- 03735193-5194 Indoor Air Standards
- 03735195 Ashrae
- 03735196 Ashrae
- 03735209-5210
- 03735211-5212 Standards Project Committee Data Form
- 03735213-5214 Ashrae 62-1981, 'ventilation for Acceptable Indoor Air Quality'
- 03735220 Ashrae
- 03735223 Ashrae Standard 62-73r
- 03735224 Ashrae Standard 62
- 03735225 Ashrae Standard 62-81 (Ansi B 194.1)
- 03735226-5233 American National Standards Institute Operating Procedures of the Board of Standards Review
- 03735234 Ashrae Standard 62-73r
- 03735235 Ashrae Standards Draft Revision 62-73r 800115
- 03735236-5237 Ashrae Standard 62-73r
- 03735238-5239 Response to Your Comments on Ashrae Standard Draft Revision 62-73r, 'standards for Ventilation Required for Minimum Acceptable Indoor Air Quality', 800115
- 03735240-5242 Appeal of Action on Ashrae Standards
- 03735243 Directory of State Building Codes & Regulations
- 03735244
- 03735245-5248
- 03735249
- 03735250
- 03735251-5252 Ashrae Tc2.3 Newsletter
- 03735253-5254
- 03735255
- 03735256 Possible Joint Sponsorship with Ashrae on A Symposium: 'cigarett Smoke and Indoor Air Quality'
- 03735257
- 03735258
- 03735259-5260
- 03735261
- 03735262-5265 Apca Tt-7 Committee Roster Indoor Air Quality
- 03735267 Ashrae
- 03735268-5334 Ventilation Requirements in Rooms by Smokers: A Review
- 03735335-5337
- 03735338-5389 Ashrae Standard Draft Revision Standards for Ventilation Required for Minimum Acceptable Indoor Air Quality
- 03735390-5422 Energy Conservation, Ventilation and Acceptable Indoor Air Quality
- 03735423-5424 Exhibit 4 Ashrae Standars Committee Roster 800000 - 810000
- 03735425-5426 Exhibit 5 800000 - 810000
- 03735427-5428 Exhibit 6
- 03735429-5448 Ashrae Standard Standards for Natural and Mechanical Ventilation
- 03735449
- 03735450 Ashrae Seeks More Ventilation in Comm. Bldgs.
- 03735451
- 03735452-5453 T.D. Sterling and Elia Sterling -- Office Building Syndrome
- 03735454-5455 T.D. Sterling and Elia Sterling -- Office Building Syndrome
- 03735456 Proposed Sterling Special Project An Investigation of Office Building Syndrome
- 03735457-5460 T.D. Sterling and Elia Sterling: An Investigation of Office Building Syndrome
- 03735461-5465 An Investigation of Office Building Syndrome
- 03735466-5468 Elia M. Sterling
- 03735469-5470 the Impact of Different Ventilation and Lighting Levels on Office Building Syndrome: An Experimental Study
- 03735471-5472 Non-Smoking Wives of Heavy Smokers Have A Higher Risk of Lung Cancer
- Litigation
- Stmn/Produced
- Author (Organization)
- Ashrae
- Characteristic
- MARG, MARGINALIA
- MISS, MISSING PAGES
- UCSF Legacy ID
- muy61e00
Document Images
A.
'( ASH RAE 621981
Ventilation
for Acceptable
Indoor Air Quality
'k.
(01981
1791 Tulli. ClrclaN.E, Atlanta, GA 30329
i

c
TABLE OF CONTENTS
FOBEWORn. pw
...................................................r
Seedo.l Parpaes ........................................................2
3eedo.2 Seoye ..........................................................2
Secdos3 Ddlnitloe. ......................................................2
Sectlo. 4 (3amHeado. ...................................:..,..............2
Section S Spt- wid Equi4-t ............................................ 2
Seetlo.6 Proeed.re .......................................................4
5eetlo.6.1 Ye.tl4do. Rate PraeMare .......................................... ,4
Section 6.1.1 Acoxphbia Outdoor Air ............................................ 4
Section 6.1.2 Outdoor Air TreaDDea . ..................................... : ...... 5
Seedo. 6.1.3 Ye.Watlo. Req.iremead ........................................... 6
Section 6.1.4 Redte.lado. Gioerlr .............................................. ,6
Section 6.1.3 YaritbkOecapaoey .............................,...,............... 6
Section 6.2 Ldoor Air Qaall ty Proceduee ....................................... ,,11
Seedo. 6.2.1 Objeed.e Meamrement. ........................................... 11
Section 6.k2 Sabjeetl.e E.aluado...,... . ....................................... 12
Section 7 Refereeca ..................................................... 13
AYpeadkea ..................................................... 14
/

!
(
FOREWORD
When Standard 62-73~ was published, a comprehensive method of establishing ventilation rates was
made available. That standard emphasized ventilation air quantitites in terms of volumetric air flow
rates
per petsonand introduced the eonceprof "acceptable outdoor air" for ventilation purposes. It also
speci'-
fied the conditions under which the outdoor air quality could be inaeased'through application of air
clean-
ing technology.
Ventilation rates in Standard 62-73 were specified' as minimum and recommended values. The recom-
mended values generally exceeded the minimum values by factors of 1.5 to 2. ASHRAE Standard 9a7S1
used mrnimum values for energy conservation purposes. ASHRAE Standard 90A-19801 reaffirmed'this
approach. This constraint and new developments in air quality control dictated that Standard 62-73
be
revised. .
The revised Standard'includes a ventilation rate procedure which indirectly controls indoor air
quality
and'a new procedure to permit direct control of the indoor air quality. The latter method may see
increas-
ing use in the future, since it gives the engineer or designer more freedbm to achieve the objective
of this
Standard and to encourage innovative solutions.
The objective of this revised Standard'is to provide healthful, and comfortable indoor environments
by
using materials and methods that optimize efficiency of energy utilization. Therefore, an
interdisciplinary
committee of engineers, physicians, chemists and psychologists was appointed to revise Standard
62-73.
ASHRAE STANDARD 62-1981
t

EXHAUST
OTHER
AIR CLEANER
LOCATION
OUTDOOR ~-- - ,F
AIR ,
(MAKEUP
AIR)
ALTERNATE
PATHS FOR
RECIRCULATED
AIR
ENERGY
RECOVERY
UNIT
AIR CONDITIONING INFILTRATION UTHER
AIR CLEANER
LOCATION
VENTILATING
AIR
OTHER
AIR CLEANER
,//~LOCATIONS-
_ i -
GENERAL,i__ LL
EXHAUST
AIR CLEANER
LOCATION
~
r~i
~
_
-
~-- LOCAL
~SUPPLY AIR ( ~ E-MAKEUP /1
j-- I _~ AIR
(
OCCUPIED _
SPACE - LOCAL
--~ EXHAUST
I ------
~-- ---~
LOCAL
VENTILATIUN
.....A.EXFIL-T-RATION
* RETURN AIR
-I
Figure 1. Ventilation System
1
r
^
N
i
00rySUCO

4.
~
C TABLE I
NATIONAL AMBIENT AIR QUALITY STANDARDS
Coatamimmr-
I.evel t.os{Term
~ Carbon Monoxide
Lead
1.5 Nv/tn3
Nitrogen IToxide
Oddants(Ozone)
Particulates
Sulfur qioxide 100 µg/tn~
75 ygJm,
80 Ng/ m,
C
.. ShortTerm
Tlme Lerel Time
40 mg/m3 t Hrl0 mg/m, 8 Hrs
3 Mo
Yr
235µg/m~ 1 Hr
Yr 2b0 yg/in3 24 Hts
Yr 363 µg/m' 24 Hrs
7er Retema 1 ~. Pamm, lnm rtpYiuon rewN Wo ee chstM. smfe re<Wruoa mer a man ,avavn ~hY.o Nos V,m
hee. and ad0i,ww wbaanm mry ee rap,iua
TABLE2
ADD[TIONAL AMBIENT AIR QUALITY GUIDELINES
Ce.orlms Lo.q Tam Simt Ta. Yd.eas
to.d Ttr l..d T1.e
Acsw.--p". 7mi/mJ 2AHn. 24mvm3 30Min l2Aaolhn_p _ 23 vvm3 C... 13 .
Ammooi.-O 0.3mYm3 Yr 7mvmj C 14;13
Bryllima 0.01 NaFm3' 30 Deys 13
Cad.,.m..,.. 2Ap/m3 24 Hn t6
CaldumOAde(Lime). 30-30yvm) C 17Cartion Disullidc--0 0.13 mvm3 ' 24 Hn 0.45 mpm, 30 Min 12
Chlorlee--O - O.Imvm3 24Hn 0.3.mg/m3 30Min 12Chromiam 1.3W/m3 7AHn 12.
CreeW-0 0.l mvm3 24 Hn. 13
picAiotoahaoe-O 2Amvm3 b4Hn 6.0mI/m3 30Mio 12FjyylAanm-0~ l4mvm I 24Hn 42m6/m3 30Min I2FarmWe6yde-p.
120µvm3 C. l3HydtoddarieAad-o 0.4mvm3 24Hn3mt/m3 30Mtn 12.13
H3dlegm Sei{ide-p 40.50 w/m7 24 Hn 42 Nvm3 ' t Hr 17 (7 tmm) .
M__P_n_p20yvm3' 1Ht l6MercarY . 2 Wlmj 24 Hn 16
Methyt Abo6oi-0 . 1.! mvm3 74 Hn 4.1 mvm3 30 Miu 12
Metayleee . 20 mvm3 Yr 130 mg/m, N! Min 14 .
.
CLloride-O 30m{/m3 24Hn 14
Nlekd 2W/mj 2414m l6.
MtroomMonowdda 0.3mvmJ 24Hn - 1!mvm3 ]0MIa 14Fpenoi-0 at mvm, 24 Hn 12.13
$rltua 4pvmj' Yr . 1712yvmj ' 24Ho (4smralldrmieAed=O30wvm3 .' Yr IOOµvm3 30Mic14.
t0pp/m7. 24Hn 14
Trichloret0yleae-0 2mvm3 Yr l6mvm,3' 30Min. 14.
3mvm~ 24Hn
Yen.dium 2Nvm~ 24Hn 16
aet 30rvm, Yr t4.
IOOyym1 24Hn 14
uyday_yp.arkd,yt.r,pd,v
mmesmnJU,lAbe-ud,eaanC.rdmnd'niemar2f'CRIFlumOeruunrn69E0mm.129.921rJelofmawtppsun.(101-3 kPe1.
'rfieu merid. merkad ..0 Aeve odas u coeaau.uor.ome,oe roeee in a,WOm av. Th. ubuWd we,mnuoa
4.db do na ns.vwdr evu4i u odnrle. coemooe..
-'CeFiee. w moimme alb..er caaamur,am.
air is not influenced by a source of substantial con-
taatination.
D. Air monitoring for three consecutive months,
as required for inclusion in the National Aerometric
Data Bank, shows that the air quality meets or exceeds
the requirements of Table 1.
Step 2: Outdoor air shall be considered unaccep-
table if it is known to contain any contaminant at a con-
centration above that listed in Table 2. This table covers
other common contaminants for which no EPA am-
blenr air quality standards existL 'i'hese levels were
selected from current practices in various states, pro-
vinces and other countries.
vinces
ministration". For application to the general popula-
tion the concentration of these contaminants should not
exceed 1/10 of the limits which are used in indtutry{see
Appendix C). In some cases, this procedure may result
in unreasonable limits. Expert consultationanay then be
required.
StepA: If after, completing steps l, 2 and 3, there is
still a reasonable expectation that the air is unaccept-
able, sampling shall be conducted in accordance with
NIOSH procedures1470' Local' and' national aerometric
data banks may contain information on some
unregulated pollutants. Finally, acceptable quality
should be evaluated using the definition in Section3.1.
6.1.2 Outdoor Air Treatment. If the outdoor air
contaminant levels exceed the values given in Section
6.1.1, the air shall be treated to control the offending
contaminants. Filters suitable for the particle size en
contami-
nant 3: If the air is thought to contain any conami-
nant not listed in Tables 1 or 2, guidance on acceptable
exposure levels should be obtained by reference to the
standards of the Occupational Safety and Health Ad-
ASHRAE STANDARD 62-1981 5

~is 111111
ffi J g g~5 ~ g ~ I I
g C w C a4 8 x i5
o ~' ~-~C r. N. u
G ..
1J
J
zo~;sUeo
C
8 8 ga 8 g g o
?
J O J
w a o u
4
u
I
0
.,
r
a

03'735 c03
0
.1
C
I
I
a°
I
I
~
P
r ~~ ~~~gb
++
s~s~
I
91tl~
~ ~
9 1
a'111
a
_ a~~ >
~ ~ ~
~^: ~ ~~~
~.~~~~~ ill
:I a a ° =1 a I a.. :1 -!a
~
I I I I ~ I
a 2 o o_ RR RRii
jll

ventilation rates, which may bLulated by a method
similar to those described in Appendix F, shallitie deter-
nrined'by the designer. The effectiveness of this system
adjustment shall be demonstratedi
6.2 INDOOR AIR QUALITY PROCEDURE: The
ventilation rate procedure described above is assumed to
provide acceptable indoor air quality, ipso jacto. Never-
theless, that procedure, through prescription of re-
quired ventilation rates, provides only an indirect solu
tiom to the control of indoor contaminants. A direct
solution would bring the concentrations of contami-
ttants to some specified,, acceptable levels. The indoor
a.
b.
C.
PROCEDURE
c
air quality procedure, described below; provides guide
lines for certain notable contaminants. It incorporates
both objective measurement and'subjective evaluationk
6.2.1 Objective Measurement. Tabies I and 2 fur-
nish information on acceptable contaminant levels in
outdoor aIr. These tables also apply indoors for the
same exposure times. Section 6.1.1. contains additional
information on contaminants.
In recenr years, problems have arisen from con-
taminanu unrelated to occupancy, but rather generated'
by the building itself and its contents. Examples include
asbestos dust, radon gas, and vapors of formaldehyde
Compute the air capacity per person in the space init"(m').
Find the required ventilation rate, in cfm (Us) per person.
Enter Figure 2 with these values and read the maximum permissible
ventilation lag time after occupancy from the intersection of
a and b.
Figure 2. Maximtm Permissible Ventilation Lag Time
ASHRAE STANDARD 62-1981 11

C TABLE4 C
SELECTED GUIDELINES FOR AIR CONTAMINANTS OF INDOOR ORIGIN
Contaminanl Conantratlons^ExDoeuteTime Comments
(
Aatone-O
Ammania-O
Asbestos
Known human carcin-
ogen, best available
control technology.
Benuae-O Known human arcin-
ogen, bat available
control technology.
Carbon Dioxidce 4.5 g/m3
ChlordAne-O 5 Ng/m3
Chlorine
Cnesol-O
Dichloromethane-O
Fonnaidehyde-O 12D yg/mJ
Hydraarbons. AliPhauc-O
Hydroarboas. Aromatie-O
Memuy
Osone-0 100 yg/m3
Pftmol-O
Radon 0.01 WorlongLevel(WL)
Continuous . See Appendix D
Continuous Reference 22
Continuous W. German and
Dutch Guidelines
Continuous
Annualaveraje Reference 24
ParaglaPh 12.6
(backsround 0.002+
0.004 WL.):
Tetrachloroettiyleoe-0
Trichlaraettlane-_0
Tutpentine-O
Vinyl Chloride-O
Known human
oudnogen, best
available control
technology.
ihsmuaiW mrW o h.w odws umecmvacr.omrtisa fosd ioiodom air. Tb. uEaWtl winenaooro do mc
n®.nry rsYU m mals ®mtiem..
- Wh.- cam.oa. uaacYfa n(w to ]a.io.6.A.1.9Wp. N0: J. Tse. mbrana rM cr for.bm tndom apowwut uAnarm
an na 7e..N.e/e.c
nose, or throat. In an absence of objective means to
assess the acceptability of such contaminants, the judg-
ment of acceptability must necessarily derive from sub-
jective evaluations of impartial observes. The air can be
considered acceptably free of annoying contaminants if
80010 of a panel of at least 20 untrained'observers deems
the air to be not objectionable under representative con-
ditions of use and occupancy. An observer should enter
the space in the manner of a normal visitor and should
render a judgment of acceptability within 15 seconds.
Fech observer should' make the evaluation indepen-
dently of other observers and without influence from a
panel leader.
REFERENCES
1. "Standards for Natural and'Mahanical Ventilation,"
ASHRAE Standard 62-73 (ANSI' B 194:1-1977). American
Society of Heating, Refrigerating and Air-Conditioning
Engineers, Inc.
2. "Energy Conservation In New Building Design,"
ASHRAE Standard 90-75, American Society of Hating,
Refrigerating and Air-Conditioning Engineers,,Ihc.
3. "Energy Conservation In New Building Design,"
ANSI/ASHRAE/[ES Standard 90A-1980; American Society
of Heating, Refrigerating and Air-Conditioning Engineers,
Inc.
4. "Thermal Environmental Conditions For Human
Ocaapancy;" ASHRAE Standard SS-I981, American Society
of Heating, Refrigerating and' Air-Conditioning Engineers,
Inc.
5. "Factory Made Air Ducts and Air Duct Connecton,.
UL 181," Underwriters Lab., 207 E. Ohio Street, Chicago, IL
60611.
6. National Fire Protection Association Std. 90A: Air-
Conditioning and Ventilating Systems, 1978. National Fire
Protection Association Std. 90B: Warm Air Heating and Air-
ASHRAE STANDARD 62-1981
13

s
velocity is no more than 2.2 m/s (5 C h). Commonly used
exhaust fans st:ch as kitchm and bathroom exhaust fans
should be turned' on. Flow of room air into the draft hood
under these conditions must indicate a 40% dilutionu of the
products of combustion going up the stack. This can be
measured by measuring the room air temperature entering the
draft hoodtHe stack temperature downstream from the draft
hood, and the flue temperature at the combustion chamber
outlet just upstream of the draft hood before the draft hood
dilution air cools the flue gas..
Then
Tr - T' _ 0:40
T. - T,
Tr - Flue Temperature
T, - Stack Temperature
T, - Room Temperature
If the stack temperature exceeds
Tt+0.4T,
T ~
~
1.4
under the measurement conditions defned above, a positive
supply of outside combustion air is needed for safe operation
of the furnace.
Power burners of the type used in oil burners have a blower
to supply combustion air. There must be enough air supplied
to this type of burner to assure th'a the burner blower pro-
duces the pressure rise specified by, the manufacturer. If a
building is so tight that the blower cannot achieve its rated'
ptesure rise, a positive supply of outdoor air must be pro-
vided. Care must be exerdsed' with oil burners, however, if
cold outdoor air is ducted directly to the burner, the low air
temperature may degrade atomization and burner efficiency.
The outdoor air provided should be temporary heat losa from
the stack and furnace jacket.
APPENDOL C
RATIONALE FOR THE USE OF INDUSTRIAL
STANDARDS OF EXPOSURE TO TOXIC AND
HAZARDOUSSUHSTANCES
Industrial health practice attempts to limit worker exposure
to injurious substances at levels which do not interfere with
the work process, and which do not injure the workers'
health. The elimination of all effects, e.g.,,unpleasant smells
or mild irritation, is not attempted. Regulations are based on
the results of accumulated experience with worker health, and
of animal experiments, carefully evaluated by groups of com-
petent experts. Exposure and effects are related to dose of the
injurious substance. Doae includes both the concentration of
the substance and the time during which it is present. Since
concentration commonly varies with time, dose is convenient-
ly expressed as a time weigtited averge concentration (TWA),
or threshold limit value (TLV). OSHA regulations are TWA's
in most cases. These are explained with examples in the intro-
duction to the reference tables". With some substances
severe reaction may be present at certain exposure concentra-
dons. Where this occurs a celing (C). or maximum allowable
concentration (MAC), is imposed in addition to the TWA so
that upward excursions in the exposure concentrations can be
kept below the aitical level. Industrial exposures are regu-
]ated on the basis of a forty hour work week with 8 to 10 hour
work days. The remainder of the time will be free ofahis expo-
sure. Since public exposure to air contaminants may be con-
tinuous rather than limited'to 40 hours per week, the TWA
should be lowered in recognition of this difference. The work
time exposure is appro dmately 1/5 of the houn in a year;
thcefore,, the allowable concentration for the general' pubilc
ASHRAE STANDARD 62-1981
C
should first be reduced to 1/5 of its value. In addition, a fur-
ther reduction to 1/10 is desirable because (1) the general pop-
ulAtion is more varied than the industrial population in sus-
ceptibility to injury due to greater variation in age and in
health status, and (2) the industrial population is often under
continual health supervision and the general population may
not be.
APPENDIX D
RATIONALE FOR MINIMUM PHYSIOLOGICAL
REQUIREMENTS FOR RESPIRATION AIR
BASED ON CO= CONCENTRATION'
Oxygen is necessary for metabolism of food to sustain life.
Carbon and hydrogen in foods are oxidized'to COi and H=O
which are eliminated by the body as waste products. Foods
can be classified as carbohydrates, fats or proteins and the
ratio of carbon to hydrogen in each is somewhat different.
The Respiratory Quotient (RQ) is the volumetric ratio of ar-
bon dioxide to the oxygen consumed. It varies from 0.71 for a
diet of 1009% fat to 0.80 for a diet of 100% protein and 1 L0 for
a diet of 100Nrcarbohydrater. A value of RQ - 0.83 applies
to the normal mix of fat, carbohydrate and protein.
The 03 required depends upon the activity level. At seden-
tary activity levd; the O=, requirement is 0.0125 cfm. If we
assume a person can consume 2S°74 of the 02 in air, then,,
since air is about 21% 02, the air required for oxygen supply
is [0.0125/(0.21x0.23)] - 0.24 cfm, clearly a small amount.
There is no problem dissipating the H20 produced by
.metabolism.
The controlling physiological factor is the CO= concentra-
tion in the inhaled aiu, not the O; limitation. People can fune-
tion at levels of COi as high as I W. (as in nuclear submarines),
but it is generally felt that 0.5 °h is a better limit (symptoms of
high COz levels are headaches and loss of judgment)i If 0.3W.
CO2 is taken as the limit, then
C02 (inspired) - COl,(outdoor air) + 2V/V
where CO= (outdoor) _ 0.03 %
N'r generation rate of C0= - 0:63 ft3 /hr per person
V- ventilation rate ft' /hr per person
CO2 (inspired) ~ 4'4 concentration
CO= (inspired) ~ (CO= (outdoor) + (0:63 x 100)/(cfm x
60)]
~ [CO= (outdoor)+ 1.05/cfm]
Solving the equation when CO, is 0.5% and lower results in
the following table for the required ventilation rate of out-
door air per person ara sedentary activity level.
4aCOs Limit du/persos
0.5 2.25
0.4 2.86
0.3 3.92
0.25 5.00
0.2 6.23
0.1 15.10
For general ventilation standards, a limit value of CO= in
the air is taken as about 0.25% as an additional safety factor,
covering individual activity, diet and health variations. The
minimum outdoor air requirement is then 5 cfm/person, and
this standard speciGes that minimum. This must be supplied
from sources outside the space, where COl levels are near
0.03% (as in outdoor air). The cfm/person is linear with
metabolic level for the same COj level, and correspondingly
higher limits are needed where activity is greater than sed-
entary air volume per person is also linear with RQ: The effect
of altitude is small, and no correction is considered necessary
to 7,000 feet, thar being well within the safety factor. (An
altitude or pressure correction table should be included for
high altitudes and special chamben.) ~
15
