Lorillard
Appendix B 'model Standards for New Structures,' Appendix J, Regional Conservation + Electric Power Plan, Section 305, Table 3-1. Ventilation (Draft, 830000).
Fields
- Alias
- 03735170/03735180
- Type
- REPT, OTHER REPORT
- CHAR, CHART/GRAPH
- OUTL, OUTLINE
- SPEC, SPECIFICATION
- CHAR, CHART/GRAPH
- Master ID
- 03735037/5472
Related Documents:- 03735038 American Red Cross Proposed Anti-Smoking Resolution
- 03735039 American Red Cross Proposed Anti-Smoking Resolution
- 03735040
- 03735041 Statement to Be Made to the Richmond Chapter of the American Red Cross (Provided by the Tobacco Institute) (Delivered by Dr. Paul Eichorn)
- 03735045-5056 Resolution I (820000) Smoking
- 03735076 American Red Cross Anti-Smoking Resolution
- 03735077 Dup of Id 03735041
- 03735078 Resolutions Presented to the American Red Cross National Convention St. Louis, Missouri, 820526 Resolution I Smoking
- 03735079-5081 American Red Cross
- 03735082-5084
- 03735085 American Red Cross
- 03735086-5087
- 03735088 American Red Cross
- 03735089 American Red Cross Anti-Smoking Resolution
- 03735090
- 03735091-5092
- 03735093 Red Cross Resolution - No Smoking Meetings/Areas
- 03735094-5095 American Red Cross Resolution Regarding Smoking in Red Cross Facilities and Associated Conferences
- 03735096 Dup of Id 03735078
- 03735097 Dup of Id 03735077
- 03735098 Smoking Policy
- 03735099-5101
- 03735102 the Attached Material - American Red Cross
- 03735103 Dup of Id 03735078
- 03735104 Board of Directors Meeting
- 03735105
- 03735106-5112 Hazards of Cigarette Smoke to Nonsmokers
- 03735113-5118 Sidestream Smoke - Fact and Fiction
- 03735119-5126 Evidence for Health Effects of Sidestream Tobacco Smoke
- 03735130
- 03735131-5132 Spc 62-1981r Roster Ventilation for Acceptable Indoor Air Quality
- 03735134-5135
- 03735136-5137 Dup of Id 03735131-5132
- 03735138-5139
- 03735141-5142 Model Variable Ventilation Requirements
- 03735143-5160 Briefing Paper Northwest Power Planning Council
- 03735161-5169 Appendix A 'pacific Northwest Electric Power Planning and Conservation Act' (Excerpt)
- 03735181-5188 Appendix C Testimony of Walker Merryman, TI, Vice-President, Northwest Power Planning Council Hearings, Boise, Id, 830311
- 03735189 Boca Medical Building Code Hearings in Cherry Hill, Nj.
- 03735190-5191
- 03735192 Ashrae
- 03735193-5194 Indoor Air Standards
- 03735195 Ashrae
- 03735196 Ashrae
- 03735197-5208 Ventilation for Acceptable Indoor Air Quality
- 03735209-5210
- 03735211-5212 Standards Project Committee Data Form
- 03735213-5214 Ashrae 62-1981, 'ventilation for Acceptable Indoor Air Quality'
- 03735220 Ashrae
- 03735223 Ashrae Standard 62-73r
- 03735224 Ashrae Standard 62
- 03735225 Ashrae Standard 62-81 (Ansi B 194.1)
- 03735226-5233 American National Standards Institute Operating Procedures of the Board of Standards Review
- 03735234 Ashrae Standard 62-73r
- 03735235 Ashrae Standards Draft Revision 62-73r 800115
- 03735236-5237 Ashrae Standard 62-73r
- 03735238-5239 Response to Your Comments on Ashrae Standard Draft Revision 62-73r, 'standards for Ventilation Required for Minimum Acceptable Indoor Air Quality', 800115
- 03735240-5242 Appeal of Action on Ashrae Standards
- 03735243 Directory of State Building Codes & Regulations
- 03735244
- 03735245-5248
- 03735249
- 03735250
- 03735251-5252 Ashrae Tc2.3 Newsletter
- 03735253-5254
- 03735255
- 03735256 Possible Joint Sponsorship with Ashrae on A Symposium: 'cigarett Smoke and Indoor Air Quality'
- 03735257
- 03735258
- 03735259-5260
- 03735261
- 03735262-5265 Apca Tt-7 Committee Roster Indoor Air Quality
- 03735267 Ashrae
- 03735268-5334 Ventilation Requirements in Rooms by Smokers: A Review
- 03735335-5337
- 03735338-5389 Ashrae Standard Draft Revision Standards for Ventilation Required for Minimum Acceptable Indoor Air Quality
- 03735390-5422 Energy Conservation, Ventilation and Acceptable Indoor Air Quality
- 03735423-5424 Exhibit 4 Ashrae Standars Committee Roster 800000 - 810000
- 03735425-5426 Exhibit 5 800000 - 810000
- 03735427-5428 Exhibit 6
- 03735429-5448 Ashrae Standard Standards for Natural and Mechanical Ventilation
- 03735449
- 03735450 Ashrae Seeks More Ventilation in Comm. Bldgs.
- 03735451
- 03735452-5453 T.D. Sterling and Elia Sterling -- Office Building Syndrome
- 03735454-5455 T.D. Sterling and Elia Sterling -- Office Building Syndrome
- 03735456 Proposed Sterling Special Project An Investigation of Office Building Syndrome
- 03735457-5460 T.D. Sterling and Elia Sterling: An Investigation of Office Building Syndrome
- 03735461-5465 An Investigation of Office Building Syndrome
- 03735466-5468 Elia M. Sterling
- 03735469-5470 the Impact of Different Ventilation and Lighting Levels on Office Building Syndrome: An Experimental Study
- 03735471-5472 Non-Smoking Wives of Heavy Smokers Have A Higher Risk of Lung Cancer
- Request
- R1-037
- Area
- LEGAL DEPT FILE ROOM
- Document File
- 03735105/03735472/S and H Re Indoor Ventilation Requirements Ashrae Boca.
- Litigation
- Stmn/Produced
- Named Organization
- Ashrae
- Northwest Power Planning Council
- Characteristic
- DRFT, DRAFT
- Date Loaded
- 05 Jun 1998
- Site
- N14
- UCSF Legacy ID
- euy61e00
Document Images
Appendix B
"Model Standard for New Structures," Appendix J, Regional
Conservation and Electric Power Plan, Section 305, Table 3-1.
Ventilation (Draft, 1983).
i

DRAFT
REGIONAL CONSERVATION
AND ELECTRIC POWER PLAN
APPENDIX 3
3anuary 26, 1983
Errata Corrected February 15, 1983
Northwest Power Planning Council
700 S. W. Taylor
Portland, Oregon
97205
i

.
w
MODL STANDARD FOR NEW STRUCNRES
Outline of Contents by
Chapter and Sections
CHAPTER 1. ADMINISTRATIVE
SEC. 100. Title .............................................. :....... 1
101. Purposes and Policies ..........:. 1
102. Scope . . . . . . . . . . . . . . . . . . . . . . . . . ..... . . . . . . . . . . . . . ... . .
... . . . . . . 2
-103. Application to Existing Buildings . 2
' 104. Materials and Equipment . . . . . . . . . . . . . . . . . . . . .
. . . . . 3
1-05. Plans and Specifications ................................... 3
106. Details .................................................... 3
107. Enforcement and Inspections
4
108. Validity ................................................... 4
109. Violations and Penalties
4
110. Liability ................................................... 5
CHAPTER 2. DEFINITIONS
SEC. 200. General ................................................... 6
201.-223. A - Z ...................................:................. 6
CHAPTER 3. DESIGN REQUIREMENTS
SEC. 300.
301.
302.
303.
General ...................................................16
..........................................................16
..........................................................16
(Reserved) ................................................. 16
304. Design Parameters ........... ........... ................. 16
305. Ventilation ................................................16
306. Methods of Compliance 22
CHAPTER 4. BUILDING DESIGN BY COMPONENTS PERFORMANCE APPROACH
General ....................................................23
(Reserved) .............. ...................................23
Overall Thermal Performances 23
Thermal Performance Criteria for
Low-Rise Residential Buildings 23
404. Thermal Performance Criteria for All Other Buildings ... 27
405. Air Leakage for All Buildings 34
406. Building Mechanical Systems 36
407. Calculations of Heating and Cooling Loads 36
408. Infiltration ................................................36
409. Simultaneous Heating and Cooling 36
410. Energy Recovery ...........................................37
411. HVAC Equipment Performance Requirements ................. 37
412. Energy for Air Delivery
45
413. Balancing ................................................. 45
414. Cooling with Outdoor Air (Economizer Cycle) .................. 47
415. Controls ..................................................47
416. Air Handling Duct System Insulation ..................... ... 49
417. "Duct Construction
49

.
'
~ MODF~ STANDARD FOR NEW STRUCTi~'S
t (Continued ~)
SEC. 418. Piping Insultation ...... .................... .49
419. Service Water Heating S7
420. Water Heaters, Storage Tanks, Boilers, and Piping S7
421. Pump Operation ............... ............ ......... .:......59
422. . (Reserved) .......................................... _......59
423. Conservation of Hot Water
S9
424. Electrical Power - General
60
-425. Electrical Distribution
426. Lighting Power_Budget ........
CHAPTER S. BUILDING DESIGN BY SYSTEMS ANALYSIS AND BUILDING
UTILIZING NONDEPLETABLE ENERGY SOURCES
SEC. 300. General ............... ******a.*-*-65
301. Energy Analysis ........ .....................................65
302. Design ....................................................65
303. Analysis Procedure ............ .................... ..... 65
504. Calculation Procedure 67
505. Documentation .............................................67
506. Buildings Utilizing Nondepletable Energy ...... ............ 048
507. Documentation - Buildings Using Nondepletable Energy Sources 68
CHAPTER 6. PRESCRIPTIVE REQUIREMENTS APPROACH
SEC. 600. General .............................................:.....69
601. Building Envelope Requirements 69
602. Building Mechanical Systems - General 78
603. Service Water Heating
80
~._ .. L
----

0
Chapter 3
DE.SIGN REQUIREMENTS
c
Section 300. General. This chapter establishes the criteria for design
of the exterior envelope of buildings and for design of the HVAC systems and
its parts, -a~nd establishes the minimum requirements for ventilation air
quality and for the minimum outdoor air quantities for ventilation. -
_ Section 301. A building designed to be both heated and cooled shall
meet the more stringent of the heating or cooling requirements provided in
this code. -
Section 302. A design feature of a building for energy conservation
shall not be approved if it would create conditions of accelerated
deterioration from moisture condensation.
'Section 303. (Reserved)
Section 304. Design Parameters. The following design parameters shall
be used for calculations required under this Standard.
a. The heating or cooling design temperatures shall be selected from
the latest edition of the ASHRAE Handbook of Fundamentals. Winter design
temperatures shall be selected from the 97.5% column. Summer design
dry-bulb and wet-bulb temperatures shall be selected from the 5% column.
b. Indoor design temperature shall be 70oF. for heating and 78oF. for
cooling. _
c. Indoor design relative humidity for heating shall not exceed 30
percent. For cooling, new energy shall not be used to control relative
humidity in the range between 30 percent and 70 percent.
Section 305. Ventilation. This Energy Standard specifies air quantities
only. For all other requirements see the Mechanical Code.
per minute (cfm) per person.
a. Minimum Outdoor Air Requirements for Ventilation. The minimum
requirements for operable window area to provide natural ventilation are
specified in the building code. If a mechanical ventilation system is provided
in lieu of operable windows for natural ventilation air shall be as specified in
this section. In areas of building where smoking is permitted, the outdoor air
quantities provided shall not be less than the smoking values listed in Table
3-1. In areas of buildings where smoking is prohibited, the outdoor air
quantities provided shall not be less than the non-smoking values listed in
Table 3-1. In no case shall the outdoor air supplied be less than 5 cubic feet
b. Heating and/or Cooling Equipment Sizing. The maximum outdoor air
quantities allowed for the purpose of sizing heating and/or cooling equipment
shall not exceed the smoking values given in Table 3-1.
-16-
.
.
.
.
..

. ~ ~ IC;-U
TABLE 3-1 C,
OUTDOOR AIR REQUIREMENTS FOR VENTILATION
. Commercial Facilities (Offices, stores, shops,
hotels, sports facilities, etc.)
Dry Cleaners and Laundries efm/person
Commercial 10 - 15 3
Storage/pick-up areas 30 35 10
Coin-operated laundries 20 35 15
Coin-operated dry cleaning 20 - 15 3
Food & Beverage Services
~ Dining rooms 70 35 7
Kitchens 20 - 10
Cafeterias, fast food facilities 100 35 7
Bars and cocktail lounges 100 50 10
Garages, Auto Repair Shops,
Service Stations
cfm/ft2 floor
4
' Par ing garages enclose - 1_._5_ 1.5
Auto repair workrooms (general) - 1.5 1.5
Hotels, Motels, Resorts, Dormitories,
and Correctional Facilities
cfm/room
5
Bedrooms (single, double 5 30 15 6
Living rooms (suites) 20 50 25 6
Baths, toilets (attached to bedrooms) 50 50 7
cfm/person
Lobbies 30 15 5
Conference rooms (small) 30 35 7
Assembly rooms (large) 120 35 7
Gambling casinos 120 35 7
Offices .~..
Office space 7 20 5 ,.,. ..
Meeting & waiting spaces 60 35 7 3rjr
Public Spaces cfm/ft2 floor
Corridors & utility rooms 0.02 0.02
cfm/stall or urinal
Public restrooms 100 75
cfm/locker
Locker & dressing rooms 50 35 15
Est. Persons -
per 1,000 ft.2
. Use if Design _
Occupancy Outdoor Air Requirements2
Type -of Occupancyl Is Unknown Smoking Smokin Notes

» \ TABLE 3-1 (Continued) C
Est. Persons
per 1,000 ft.2
Use if Design
Occupancy
utdoor Air Requirements2
Type of Occupancyi Is Unknown Smokin Sm. oking Notes
Retail Stores cfm/person
Sales floors & showrooms
Basement & street floors
30
25
5
Upper floors 20 25 5
Storage areas (serving sales
and storerooms)
15
25
5
Dressing rooms - 25 5
Malls & arcades 20 10 5
Shipping & receiving areas 10 10 5
Warehouses 5 10 5
Elevators - - 15
Smoking rooms 70 50 -
Speciality Shops cfm/person
Barber & beauty shops 25 35 20
Reducing salons, health spas
(exercise rooms)
-20
-
15
Florists 10 25 5 8
Show repair shops (combined
workrooms/trade areas)
10
15
10
cfm/ft2 floor
Pet shops - 1 1
Sports & Amusement Facilities cfm/person
Ballrooms & discos 100 35 7
Bowling alleys (seating area) 70 35 7
Playing floors (e.g., gymnasiums,
ice arenas)
30
-
20
9
Spectator arenas 150 35 7
Game rooms (e.g., cards &
billiards rooms)
70
35
7
Swimming pools cfmlft2 area
Pool & deck areas - - 0..5 ! 0
cfm/person
Spectators area 70 35 7
Theatres cfm/person
Ticket booths - 20 5
Lobbies, foyers & lounges,
& auditoriums in motion
picture theatres, lecture,
concert & opera halls '
50
5
7
Stages, TV & movie studios 70 - 10 11 p
w
~
-18- C~1N
~
a7
~

4
C TABLE 3-1 (Continued) C
Persons
Est
.
per 1,000 ft.2
Use if Design
Occupancy
Outdoor Air Requirements2
Type of Occupancy 1 Is Unknown Smoking Smoking Notes
Transportation
Waiting rooms, ticket &
baggage areas, corridors
& gate areas, platforms, -
concourses 150
35
7
12
Workrooms cfm/person 13
Meat processing rooms 10 - 5
Pharmacists' workroom 20 - 7
Bank vaults 10 - 5
Photo studios
Camera room, stages 10
-
20
cfm/ft2 floor
Duplicating & printing rooms - 0.5 14
Institutional Facilities
(Educational facilities, hospital, nursing & convalescent homes)
Educational Facilities cfrrm/person
Classroom 30 25 5
Laboratories 30 - 10 15
Training shops 30 35 7
Music rooms 50 35 7
Libraries 20 - 5
Hospital, Nursing & Convalescent Homes cfrn/bed 16
Patient rooms 10 35 7
cfm/person
Medical procedure areas 10 35 7 17
Operating rooms, delivery rooms 20 - 40 17
Recovery & intensive care rooms 20 - 15 17
Autopsy rooms 20 - 100 18
Physical therapy areas 20 - 15
O
CJ
Q
-19- W
V
H
~
~
i

h
.
TABLE 3-1 (Continued)
Est. Persons
per 1,000 ft.2
Use if Design
Occupancy
Type of Occupancy 1 Is Unknown
c-
Outdoor Air Requirements2
Smokin Smokin Notes
Residential Facilities
(Private dwelling places, single or multiple, low or high rise)
Residential Facilities cfm/room 19
General living areas 10 20
Bedrooms 10 20
All other rooms 10 20
.
Kitchens 100: 20,21
Baths, toilets 50 20,21
Garages (separate for each cfm/car space
dwelling unit) 100
cfm/ft2 floor
Garages (common for several units) 1.5
, Industrial Facilities
Industrial Facilities
cfm/person
22
High activity level (2.5 met) 35 20 23,24
Medium activity level (2.0 met) 35 10 23,24
Low activity level (1.5 met) 35 7 23,26
1. In the case of an occupancy type not specifically mentioned, the requirements shall
be determined by the building official based on the most comparable occupancy
type specified.
2. These values are based on ASHRAE Standard 62 "Ventilation for Acceptable Indoor
Air Quality". A blank (-) indicates that smoking or nonsmoking in aspace should
not occur. In these instances for the purposes of this Energy Code, the
corresponding smoking or non-smoking maximum value shall apply.
3. Dry cleaning processes may require more air.
4. Distribution must consider worker location and concentration of running engines;
stands where engines are run must incorporate systems for positive engine exhaust
withdrawal.
5. See also food and beverage services, merchandising barber and beauty shops,
garages.
6. Independent of room size.
7. Independent of room size: installed capacity for intermittent use. p
-20-
i

_ , S . . .
.
8: Ventilation to optim3..- plant growth may dictate requireents.
9. When internal combustion engines are operated for maintenance of playing
surfaces, increased ventilation rates will be required.
10. Higher values may be required for humidity control.
11. Special ventilation will be needed to eliminate special stage effects (e.g. dry ice
vapors, mists, etc.)
12. . Ventilation within vehicles will require special consideration.
13. Spaces maintained at'low temperatures (-10oF to +S0oF) are not covered by these
requirements unless the occupancy is continuous. Ventilation from adjoining spaces
is permissible. When the occupancy is intermittent, infiltration will normally
exceed the ventilation requirement.
14. Installed equipment must incorporate positive exhaust and control (as required) of
undesirable contaminants (toxic or otherwise).
15. Special contaminant control systems may be required for processes or functions
including laboratory animal occupancy.
16. Special requirements or codes and pressure relationships may determine minimum
ventilation rates and filter efficiency.
17. Procedures generating contaminants may require higher rates.
18. Air shall not be recirculated into other spaces.
19. Operable windows or mechanical ventilation systems shall be provided for use when
occupancy is greater than usual conditions or when unusual contaminant levels are
generated within the space.
20. Ventilation is independent of room size.
21. Installed capacity for intermittent use.
22. Occupational safety laws usually regulate process ventilation requirements. The
followign list gives the requirements for the occupants only.
23. 1.0 met = sedentary activity level = 18.4 Btu/hft2 body surface.
24. Mining, foundry, etc.
.25. Automotive repair, assembly liae, etc.
26. Laboratory work, light assembly, etc.
~
-21- C.:
.z.
N
~
CD
i
